York R-410A ZH/ZJ/ZR Series Benutzerhandbuch

Seite von 206
528150-YTG-G-1210
Johnson Controls Unitary Products
87
75°F
85°F
2125
72
42.8
6.3
-
-
-
-
-
37.6
6.4
-
-
-
-
-
67
35.4
6.5
1.6
1.5
1.4
1.2
-
28.6
6.8
-
-
-
-
-
62
31.9
6.2
4.4
4.3
4.2
4.1
4.0
24.7
6.5
-
-
-
-
-
2550
72
50.9
6.2
-
-
-
-
-
48.3
6.4
-
-
-
-
-
67
42.1
6.4
6.2
5.4
4.7
3.9
-
37.3
6.8
3.3
2.9
2.5
2.0
-
62
38.0
6.1
16.6
15.8
15.0
14.3
13.5
32.5
6.5
13.0
12.5
12.1
11.6
11.2
57
29.4
6.1
16.6
15.8
15.0
14.3
13.5
22.5
6.4
10.6
10.1
9.7
9.3
8.8
2975
72
59.1
6.2
-
-
-
-
-
58.9
6.3
-
-
-
-
-
67
48.9
6.4
10.8
9.4
8.0
6.6
-
46.0
6.7
7.9
6.8
5.7
4.6
-
62
44.0
6.1
28.7
27.3
25.9
24.5
23.1
40.2
6.4
26.6
25.5
24.4
23.3
22.2
57
34.1
6.0
27.7
27.3
25.9
24.5
23.1
28.4
6.4
22.4
22.2
21.1
20.0
19.0
3400
72
67.2
6.2
-
-
-
-
-
69.6
6.3
-
-
-
-
-
67
55.6
6.3
15.4
13.3
11.3
9.2
-
54.7
6.7
12.5
10.7
9.0
7.3
-
62
50.1
6.0
40.9
38.8
36.8
34.7
32.6
48.0
6.4
40.2
38.5
36.7
35.0
33.3
57
38.8
6.0
38.8
38.8
36.8
34.7
32.6
34.3
6.3
34.3
34.3
32.6
30.8
29.1
3825
72
68.6
6.1
-
-
-
-
-
69.7
6.2
-
-
-
-
-
67
56.7
6.3
19.7
17.0
14.4
11.7
-
54.6
6.6
17.2
14.9
12.5
10.2
-
62
51.1
6.0
46.5
45.5
42.8
40.1
37.5
47.9
6.3
45.3
45.4
43.1
40.7
38.3
57
39.6
5.9
39.6
39.6
36.9
34.3
31.6
34.0
6.3
34.0
34.0
31.6
29.3
26.9
4250
72
69.9
6.1
-
-
-
-
-
69.8
6.2
-
-
-
-
-
67
57.8
6.3
24.0
20.8
17.5
14.2
-
54.5
6.6
22.0
19.0
16.0
13.1
-
62
52.1
5.9
52.1
52.1
48.8
45.6
42.3
47.7
6.3
47.7
47.7
47.7
46.4
43.4
57
40.4
5.9
40.4
40.4
37.1
33.9
30.6
33.7
6.2
33.7
33.7
30.7
27.8
24.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower 
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR102 (8.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
85
80
75
70
65
85
80
75
70
65