NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
1
General Information
Modules, Systems, and Groups
NetworkAIR Modules and Expansion Modules can be combined electronically to create Systems 
and Groups.
Module
Module is an independent Computer Room Air Conditioner (CRAC) that operates 
based on its own temperature and humidity sensors.
System
System is a set of one to three Modules or CRACs. System 
operation is based on an average of the combined temperature and 
humidity sensors of all the Modules in the System. The Modules in a 
System work together as a single unit to increase cooling capacity.
In a System, one of the Modules is designated as the Main Module and the rest of modules are 
designated as Expansion Modules. The Main Module is the controller for all the Modules in the 
System. It contains the Programmable Customer Input/Output Module (PCIOM) boards, the 
webcard, and establishes communications with the Building Management System (BMS). 
Note: When using the System configuration, only the Main Module display will be 
operational. The Expansion Module displays will not operate.
 Main Module
 Expansion Module 1
 Expansion Module 2