American Power Conversion DX Benutzerhandbuch
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
6
Using the Display Interface
Scrolling status screens
The first time you apply power to the Module, the display initializes and runs an LED and alarm-
tone test.
tone test.
After start-up, the interface displays the firmware revision number (if the fast start-up is disabled).
The display interface then scrolls automatically and continuously through the following nine screens
of status information.
The display interface then scrolls automatically and continuously through the following nine screens
of status information.
Press the up or down arrow key to interrupt the automatic scrolling and view a specific status screen.
To return to the scrolling status screens, press the
To return to the scrolling status screens, press the
E
SC
key from the main menu screen.
Status Screen Name
Status Information Displayed
Control Temp & Humidity
• Temperature and humidity at the sensors being used to control the
environment
• Remote Temperature and Humidity (optional)
• Humidity Control Method (dew point or relative humidity)
• Humidity Control Method (dew point or relative humidity)
Cool/Dehum Demands
• Cool Demand %
• Dehumidify Demand %
• Actual Output %
• Dehumidify Demand %
• Actual Output %
Reheat Demand
• Reheat Demand %
(Electric SCR only)
Humidify Demand
• Humidify Demand %
• Humidify Actual %
• Humidify Actual %
Group Status
• Number of Systems
• Setpoint Share: On/Off
• Demand Fighting: On/Off
• Setpoint Share: On/Off
• Demand Fighting: On/Off
Group Status
• System number
• Role
• State
• Role
• State
Active Alarms
• Alarm number
• Module identifier
• Alarm name
• Time stamp
• Module identifier
• Alarm name
• Time stamp
Setpoints
• Cool °C (or °F)
• Reheat °C (or °F)
• Reheat °C (or °F)
Setpoints
• Dehumidify % RH
• Humidify % RH
• Humidify % RH