American Power Conversion DX Benutzerhandbuch

Seite von 96
37
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
Modes
Path: Main > Control Environment > Modes 
Enable and disable the modes of operation. The four modes are:
•   Cool
•  Reheat
•   Dehumidify
•   Humidify
Modes can only be enabled or disabled using the service password.
Essential functions
Path: Main > Control Environment > Essential Functions 
Designate each mode as either essential or nonessential. The modes 
marked as nonessential are disabled when an alarm or event occurs that 
requires all nonessential operations to be stopped (nonessential 
lockout).
See “Input contacts” on page 25 for a table with descriptions of how you can set up 
nonessential lockout events that occur when an input contact becomes active.
Cool:      Enabled
Reheat:    Disabled
Dehumid:   Enabled
Humidify:  Enabled
na
04
30a
Cool:    Essential
Reheat:  Nonessent.
Dehumid: Nonessent.
Humidify:Nonessent.
na
04
31
a