Operation: Set Up Contacts and Relays
14
NetworkAIR IR Operation, Maintenance, and Troubleshooting
Action. 
Set the System controller to respond to the change of status for an input in one of the 
following ways:
Output relays
Path: Main > Setup > System # > Input/Output > Output Relays
The Main Module supports up to 16 user-defined output relays. Output relays respond to internal 
alarms and events by changing state to notify outside devices.
Relay Out. 
Choose the relay number to view or modify.
Map. 
Choose alarms or events to map to this relay: 
• The first line of the map field displays the location of the event that is mapped to this relay. It 
can be a System, Main Module, Expansion Module 1, or Expansion Module 2 event.
• The second line displays the name of the event mapped to this relay.
State
Map
Description/Function
Status Only
Displays the event on the Active Alarms 
screen. Status-only events are not logged.
Minor Alarm
Activates the Warning LED and the alarm 
beeper. It also creates an entry in the event log.
Major Alarm
Activates the Alarm LED and the alarm 
beeper. It also creates an entry in the event log.
Remote Run/Stop
Shuts down the Modules normally, waiting for 
delay timers.
Nonessential Lockout
Deactivates modes set as nonessential and 
continues operation.
Immediate Shutdown
Shuts down the Modules immediately. It does 
not wait for the blower delay or compressor 
timers.
Note
Any input contact and output relay available in this System can be mapped to this relay.