American Power Conversion Central Air Conditioning System Benutzerhandbuch

Seite von 84
Operation: Control the Environment
NetworkAIR IR Operation, Maintenance, and Troubleshooting
23
PID controls
Path: Main > Setup > System # > System Config > PID Controls
The Proportional plus Integral plus Derivative (PID) loop is used to control the output of the cool, 
reheat, and dehumidify modes. 
Choose which mode or actuator PID loop to tune, using the 01of03: [Mode/Actuator name] setting.
Mode. 
Choose the multipliers to use in the PID algorithm. You can omit the derivative or the integral 
and derivative multipliers in the algorithm.
P. 
The proportional multiplier (gain) for this mode or actuator. The proportional multiplier adjusts for 
the difference (error) between the measurement (temperature or humidity) and the setpoint. The 
proportional multiplier is expressed in percent of output per unit error. 
I. 
The integral multiplier (reset rate) for this mode or actuator. The integral multiplier adjusts for error 
measurement, and the amount of time that the error has existed. The integral multiplier adds to or 
subtracts from the output in small increments to correct for the offset error caused by the proportional 
contribution. It is expressed in percent of output for each minute and unit of error (error multiplied by 
minutes).
D. 
The derivative multiplier (derivative) for this mode or actuator. The derivative multiplier adjusts 
the output for rapid changes in the error, correcting for the rate of change of the error over time. It is 
expressed in percent of output for each unit of error per minute (error divided by minutes).