Operation: Respond to Alarms
NetworkAIR IR Operation, Maintenance, and Troubleshooting
43
Humidifier Cylinder Depleted
• Replace the disposable cylinder.
• Clean the reusable humidifier cylinder (optional).
Humidifier Cylinder Full when 
Off
• Check the humidifier drain valve for clogging.
• Check the operation of the humidifier drain solenoid.
Humidifier Drain Malfunction
• Ensure that the drain is free of any debris.
• Verify the operation of the drain solenoid valve.
Humidifier Excessive Foam
• Verify that the humidifier water supply is not using conditioned water and 
that the water does not contain contaminates.
• Check the humidifier water supply hose for dirt and contaminates.
• Check the steam supply hose for kinks that may cause back-pressure.
Humidifier Excessive Output 
Reduction
• Reduce the humidifier sensitivity setting on the display interface (Path: 
Main > Setup > System # > System Config > Humid. Sensitivity) if 
necessary.
Humidifier Fault Tolerance 
Exceeded
• The humidifier has experienced three faults within one-half hour.
• Reset the humidifier from the display interface (Path: Main > Setup > 
Module > [Module in which the alarm occurred] > Module Control > 
Reset Humidifier
).
Humidifier Internal Memory 
Error
• Check the controller connections to the humidifier for electrical discharge.
Humidifier No Power
• Verify that the circuit breaker for the humidifier has not been tripped.
• Confirm that the line voltage connections to the cylinder are secure and 
correct.
Humidifier Requires 
Maintenance
• Verify the operation of the humidifier and perform preventive maintenance.
• Reset the maintenance alarm on the display interface for the humidifier.
Humidifier Water Conductivity 
High
• Verify that the proper voltage is being applied to the humidifier cylinder.
• Confirm that the line voltage connections to the cylinder are secure and 
correct.
• Ensure that the water supply to the humidifier has not been conditioned. 
Conditioned water can increase water conductivity.
Humidifier Water Level Low
• Verify that the humidifier water supply is open and flowing to the humidifier 
water connection.
• Confirm that the inlet water strainer on the humidifier fill solenoid is clear 
and free of debris.
• Ensure that the water pressure is at least at 30 psig (206 kPa).
• Verify the operation of the fill solenoid valve.
Module Powered Up
• The Module has successfully started.
No Backup Systems Available
• Check the number of Systems designated for the backup role. 
• Check that the backup Systems are not failed, in the Comm Lost state, or Off.
Primary Sensors Failed
• Verify that there is a proper CAN connection between sensors and the user 
interface box.
• Replace the sensor assembly.
Remote Sensor Removed
• Check the CAN bus connection to the remote sensors.
• Disregard if you removed the remote sensor.