American Power Conversion Central Air Conditioning System Benutzerhandbuch

Seite von 84
Network Management Card: Quick Configuration
NetworkAIR IR Operation, Maintenance, and Troubleshooting
51
Local access to the control console
You can use a local computer that connects to the NetworkAIR IR System through the serial port on 
the control board to access the control console. Whenever possible access the control panel through a 
network connection. 
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the configuration cable (APC part 
number 940-0103) to connect the selected 
port to the serial port (J2) on the 
controller board. The controller board is 
in the right compartment of the electrical 
panel.
3. Run a terminal program (such as 
HyperTerminal) and configure the 
selected port for 2400 bps, 8 data bits, no 
parity, 1 stop bit, and no flow control, and 
save the changes.
4. Press 
E
NTER
 to display the User Name prompt.
5. Use apc for the user name and password.
6. See “Control console” on page 52 to finish the configuration.
The procedure requires the front door and right side (low voltage) of the 
electrical panel of the NetworkAIR IR In-row Precision Air Conditioner to be 
open, which creates an electrical hazard. 
Do not touch components on 
the electrical panel, other than 
the serial port.
Serial Port (J2)
Network Management Card