NetworkAIR IR Operation, Maintenance, and Troubleshooting
67
Troubleshooting
Refrigeration
Problem
Possible Cause
Corrective Action
Controls are erratic 
or inoperative
• Incorrect secondary voltage.
• Ensure that the control transformer secondary 
voltage is within +/- 10% of 24 VAC.
• Remote shutdown input is 
cycling the Module on and 
off.
• Check the event log for an entry in the log that 
indicates remote shutdown activity.
Evaporator motor 
fails to start
• Control circuit breaker is 
tripped.
• Reset the control circuit breaker.
• Frequency Drive is in an 
alarm condition or has failed.
• Check the event log for a VFD alarm entry. 
Replace the frequency drive.
Humidifier 
inoperative
• Humidifier circuit breaker 
tripped.
• Water supply strainer may be 
clogged.
• Improper water supplied to 
humidifier.
• Non-essential lockout has 
been activated by a user-
defined input with the 
equipment.
• Check for short circuit. Reset the circuit breaker.
• Remove and clean the strainer.
• For proper operation, the humidifier requires a 
regular water supply. Any treated water 
(demineralized, softened, or ionized water) will 
result in improper humidifier operation.
• Review the event log to see if this alarm input has 
been activated.
Reheat elements 
inoperative
• Circuit breaker is open.
• Non-essential lockout has 
been activated by a user-
defined input with the 
equipment.
• Check for direct short circuits. Reset the circuit 
breaker.
• Review the event log to see if this alarm input has 
been activated.
Airflow too Low
• External static pressure is too 
high.
• The pressure drop across the 
chilled water coil is below 
the recommended value.
• Cooling setpoint is too low. 
• Try to compensate by increasing the blower speed 
to match recommended coil pressure drops.
• Raise the Module to the minimum height or add 
duct transitions to direct the air across the floor.
• Check the chilled water coil pressure drop through 
the display interface. Pressure should match 
recommended pressure drops indicated on the 
chart based on Module size. If the pressure drop is 
below the recommended settings, increase the 
blower speed until the pressure drop matches the 
recommended setting. See “Calibrate airflow 
manually” on page 17.
• Verify that the cooling setpoint is not below 68° F 
(20° C).