 Installation and Service Manual Upsilon-Series 
30
7.6  Condensate vent collective flue gas outlet system
Flue gases condensate inside the outlet system. Anticipate approx. 1 litre of con-
densate per m3 of natural gas spent on heating. The resulting condensate has to be 
drained.
Therefore, collective flue gas outlet systems have to be fitted with a condensate drai-
nage facility. Using a plastic siphon, the drainage is connected to the sewage system 
by means of an open connection. The diameter of the condensate drainage is 40 mm 
and may be made of PVC.
The condensate drainage of the flue gas vent system may be combined with the boi-
lers´ condensate pipe work headers.
Draining condensate water on the rainwater drainage is not allowed due to the
risk of freezing.