A.O. Smith 140 Benutzerhandbuch

Seite von 68
 Installation and Service Manual Upsilon-Series 
37
9
Boiler control
The boiler has a control unit. This control takes care of most of the manual settings but 
also provides numerous settings to adjust the control exactly to the installation and user 
requirements.
Display
The LCD screen is backlit. The light is activated by pushing one of the buttons. 
There are 3 light colours available.  The various colours indicate the following:
Blue 
Basic level
Green 
Setting level
Red 
Problem display (flashing)
Having pressed a button, the screen light stays on for 2 minutes (blue screen) or 20 
minutes (green screen). 
Screen explanation
 
 
 
 
10 
11 
12    13
1   
 
 
 
 
 
 
 
5
2   
 
 
 
 
 
 
 
6
3   
 
 
 
 
 
 
 
7
4   
 
 
 
 
 
 
 
8
1.  CH-program active
2.  DHW-program active
3.  Clock program active
4.  Pump continuously active or pumps active when frost protection is active
5.  Boiler off at outside temperature > T-day (when day temperature is active)
 
 
 
 
or 
> T-night (when night temperature is active)
6.  System pump on
7.  Burner on. Starts flashing during ignition, continuous when burner is on 
8.  Chimney sweep function (100% power for emission measurement) 
9.  Boiler address:
 
1  
= Cascade Master
 
2.8 
= Cascade Slaves
10. Identification burner inside boiler
11. Night temperature active
12. Day temperature active
13. 2 text lines with 8 characters each
A B C D
E F G H
Boiler symbols are not visible in case of a single boiler 
or when no bus communication cable is connected  
(Message code M024sc08).