A.O. Smith 140 Benutzerhandbuch

Seite von 68
 Installation and Service Manual Upsilon-Series 
52
13.2.2
Check O
2
The O
2
percentage is set by the factory. It has to be checked during inspection,
maintenance and faults.
It can be checked as follows:
-  Ensure that the boiler is at maximum load and can dump the heat generated; 
-  Press down the arrow buttons simultaneously for 2 seconds. 
 
The screen turns green;
-  Press the right arrow button until you see Service chapter.;
-  Press OK; 
 
The screen displays Throttle;
-  Press OK;
 
The screen displays Throttle off;
Only for UB 110 and UB 140: 
-  Press the right arrow button to select burner A.
 
The exchanger symbol displays the selected burner (AB, A or B)
-  Calibrate the O
meter ;
-  Position the lance of the O
2
 meter into the flue outlet test point (refer to fig. 13.2.2.a); 
-  Press on the + button until the maximum value (in kW) has been reached; 
 
The boiler will be burning at the rated full capacity (value on display in %)
-  Leave measuring O
2
 to the measuring equipment.
 
Natural gas
Propane
-   O
2
percentage at full load =  4,7% (-1,2%, +0,8%)  5,1% (-1,2%, +0,7%)
CO
2
percentage at full load =  9,0% (-0,4%, +0,6%)  10,3% (-0.4%, +0.8%)
-  If required, you may turn the setting screw to set the correct O
2
 percentage.
 
(refer to fig. 13.2.2.b).
Finally, the O
2
percentage at low load must be checked:
-  Press on the - button until the value1 has been reached. 
  The boiler will be burning at low capacity (value on display in %).
-  Leave  measuring  O
2
  to  the  measuring  equipment  and  check  if  the  measured  O
2
 
percentage on low load is between following values:  
 
Natural gas
Propane
-  O
2
percentage at low load between  5,0% and 7,0%
5,1% and 7,0%
CO
2
percentage at low load between  7,7% and 8,8%
9,1% and 10,3%
Contact A.O. Smith when the measured values is outside this range.  
End of measuring:
-  Press the – button until off is displayed (keep pushed down). 
 
 
This ends the procedure for burner A. 
Only for UB 110 and UB 140: 
-  Press the return button 1x
-  Press the right arrow button to select burner B.
 
The exchanger symbol displays the selected burner (AB, A or B)
 
Repeat the procedure for burner B.
-  Press the return button to return to the original read-out.
Measuring point                       figure 13.2.2.a
adjusting screw              figure 13.2.2.b