Error report
On the display, errors found are shown in the form of  a message or blocking on a blue 
screen or an error on a red screen.
-  Blocking 
This is a temporary error that will sort itself out, or it will block the
 
 
 
boiler after several attempts (error)(Except: Bx01sc01 = reset)
-  Error   
Error implies a blocking of the boiler and can only be solved by a
 
 
 
reset and/or intervention of a service engineer. 
-  Message 
Implies a message such as low water pressure, but the device will
 
 
 
remain operational. 
 
 
 
Point of attention requiring short-term intervention. 
The code consists of a Main Code and a Subcode
Main code  Blocking  
= B
Main code Error    
= E
Main code Message 
= M
Followed by a character 
0 = boiler
 
 
 
 
1 = burner A
 
 
 
 
2 = burner B
Subcode always starts with  sc
Bx01sc01  Fan does not run on correct speed (Reset necessary). Fan defective.
Bx03sc01*  Flow sensor T1 open
Bx03sc02*  Flow temperature T1 too high 
Bx03sc03*  Flow sensor T1a open
Bx03sc04*  Flow temperature T1a too high 
Bx05sc01*  Return sensor T2 open
Bx05sc02*  Return temperature T2 too high
Bx08sc01*  General purpose contact open
Bx12sc01*  Water pressure sensor open
Bx12sc02*  Water pressure sensor closed
Bx12sc03*  Water pressure lower than 0.7bar. Top up
Bx12sc04*  Water pressure too high. Decrease pressure
Bx12sc05*  No pressure increase on pump start
Bx13sc01*  DT  between T1 and T2 too high
Bx15sc01*  Communication error between controls
Ex01sc01*  Fan does not run on correct speed. Fan defective. 
Ex02sc01*  No flame after 4 start attempts
Ex02sc02*  Insufficient ionisation 
Ex04sc01*  Flow temperature T1 too high
Ex04sc02*  Flow sensor T1 closed
Ex04sc03*  Flow temperature T1a too high
Ex04sc04*  Flow sensor T1a closed
Ex06sc01*  Return temperature T2 too high
Ex06sc02*  Return sensor T2 closed
Ex18sc01*  Unwanted flame forming
Ex14sc01*  DT not fast enough
Ex14sc02*  DT between T1 and T2 > 35°C
M024sc01  DHW sensor T3 open (when P122=1)
M024sc02  DHW sensor T3 closed (when P122=1)
M024sc03  Outside sensor T4 open
M024sc04  Outside sensor T4 closed
M024sc05  Common flow sensor T10 open
M024sc06  Common flow sensor T10 closed
M024sc08  Bus communication: Possibly no bus communication cable connected
Mx24sc09  Temperature increase (Gradient) not fast enough after burner start
Mx24sc10  DT between T1 and T2 > 35°C when gas valve opened
* When this code is shown with an M instead of a B or E then a reset with the reset button is possible.
OpenTherm error mes-
sages
The coding of the trans-
mitted Error Messages
on a OpenTherm con-
troller is displayed as
follows:
(E) EB (E = Error Code =
B and boiler number)
example: Error Code
Ex02SC02 on boiler 6
will appear as (0) 26