VI.  Electrical
A.
  General. Install wiring and electrically ground boiler 
in accordance with authority having jurisdiction or, in 
the absence of such requirements, follow the National 
Electrical Code, NFPA 70, and/or CSA C22.1 Electrical 
Code.
B.
  A separate electrical circuit must be run from 
the main electrical service with an over-current 
device/disconnect in the circuit.  A service switch is 
recommended and may be required by some local 
jurisdictions. Install the service switch in the line 
voltage “Hot” leg of the power supply.  Locate the 
service switch such that the boiler can be shut-off 
without exposing personnel to danger in the event of 
an emergency.  Connect the main power supply and 
ground to the three (3) boiler wires (black, white and 
green) located in the junction box at the inside top of 
the boiler jacket.  If a low water cutoff is to be used, 
connect the low water cutoff so that all 120V power 
to boiler is interrupted if the low water cutoff’s switch 
opens.
C.
  Refer to Figures 28 and 29 for details on the internal 
boiler wiring.
DANGER
Positively assure all electrical connections are unpowered before attempting installation or service of 
electrical components or connections of the boiler or building.  lock out all electrical boxes with padlock 
once power is turned off.
WARNING
Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source.  Make sure all power is off before attempting any 
electrical work.
Each boiler must be protected with a properly sized over-current device.
Never jump out or make inoperative any safety or operating controls.
The wiring diagrams contained in this manual are for reference purposes only.  Each boiler is shipped with 
a wiring diagram attached to the front door.  Refer to this diagram and the wiring diagram of any controls 
used with the boiler.  Read, understand and follow all wiring instructions supplied with the controls.
NOTICE
All wire, wire nuts, controls etc. are installer supplied unless otherwise noted.
NOTICE
This boiler is equipped with a high water temperature limit located inside the internal wiring of the boiler.  
This limit provides boiler shutdown in the event the boiler water temperature exceeds the set point of the 
limit control.  Certain Local Codes require an additional water temperature limit.  In addition, certain types 
of systems may operate at temperatures below the minimum set point of the limit contained in the boiler.
If this occurs, install an additional water temperature limit (Honeywell L4006 Aquastat) located in the system 
piping as shown in the Water Piping and Trim Section of this manual.  Wire as indicated in the Electrical 
Section of this manual.