FREEZE PROTECTION
CAUTION
Keep appliance area clear and free from combustible
materials, gasoline and other flammable vapors and
liquids.
4.
As the appliance comes on and fires, record the
inches of water column of displacement on both
sides of the manometer. The sum of these two 
readings as they are effected by the two air 
pressures is the differential air pressure.
5.
The differential air pressure should be 3.5 inches 
of water column (+ 0.1” w.c.) when the burner is 
firing at 100% of rated input.
6.
If the differential air pressure is not 3.5 inches 
water column (+ 0.1” w.c.), review the installation.  
Check for proper installation of the venting 
system. Review the venting requirements in this 
manual for the specific venting system installed 
with this appliance. Correct as required. Ensure 
that an adequate supply of combustion air is 
supplied to the appliance. If a separate pipe is used 
to supply combustion air, ensure that it is installed 
per the combustion air pipe requirements 
contained in the venting section of this manual. 
Correct as required. Check the air inlet screen to 
the combustion air blower. Clean as required. 
Check the burner for dirt or contamination and 
clean as required. Recheck for correct differential 
air pressure after correcting an installation related 
problem or after cleaning an obstructed 
component. Ensure that a combustion air 
differential of 3.5 inches water column (+ 0.1” w.c.)
is present while the appliance is firing at 
100% of rated input.
7.
This is a reference pressure only and is not field 
adjustable. An appliance supplied with an 
unrestricted supply of combustion air from a 
correctly sized combustion air opening or separate 
direct vent combustion air pipe will operate at the 
correct air pressure differential as the burner input 
varies with temperature demand.
8. 
Close the two air pressure test cocks on the 
pressure test tree and remove the hoses to the 
manometer.
9.
Close the front control panel.
L.   COMBUSTIBLE  MATERIALS 
Installations are not recommended in areas where the danger of
freezing exists.  Proper freeze protection must be provided for
appliances installed in unheated mechanical rooms or where
temperatures may drop to the freezing point or lower.  If freeze
protection is not provided for the system, a low ambient temperature
alarm is rec om mend ed for the mechanical room.  Damage to the
appliance by freezing is non-warrantable.
1.
Pump Operation - MOST IMPORTANT - This 
appliance is designed for con 
tin 
ous pump 
operation when the burners are firing. The integral 
circulating pump will run continuously when the power
switch is in the “ON” position and the run/stop switch is
in the “RUN” position.  As an optional feature an
intermittent pump control system can be provided.  The 
intermittent pump option allows the integral circulating 
system pump to be cycled on at each call for heat and
cycled off when the set point is satisfied.  The 
intermittent pump will operate for a timed period after 
the burner cycles off to remove residual heat from the 
combustion chamber area.  If the operating temperature
sensor for an intermittent pump system sees a drop in
water temperature to 45°F (7.2°C), the integral
circulating pump will cycle on.  This flow of warm boiler
water can help prevent freezing.
2.
Location  - Heating boilers, hot water supply boilers 
or water heaters must be located in a room having 
a temperature safely above freezing [32°F(0°C)]. 
3.
Caution - A mechanical room op 
er 
at 
ing under a 
negative pressure may experience a downdraft in 
the flue of an appliance that is not firing.  The cold 
outside air may be pulled down the flue and freeze 
a heat exchanger.  This condition must be corrected to
provide adequate freeze protection.  
4.
A motor driven damper may be installed in the air inlet to
prevent cold air movement in cold climates.  The damper
MUST be interlocked with boiler/water heater controls to
open and prove on a call for heat.
5. 
Freeze protection for a heating boiler or hot water 
supply boiler using an indirect coil can be provided by
using hydronic system antifreeze. Fol 
low the 
manufacturers instructions. DO NOT use undiluted 
or automotive type antifreeze.
6. 
Shut-down and Draining - If for any reason, the 
unit is to be shut off, the following precautionary 
measures must be taken:
(a)   Shut off gas supply.
(b)   Shut off water supply.
(c)   Shut off electrical supply.