NOTICE
Accessories  for  woodstoves  for  clearance  reduction  have
been  developed  by  many  manufacturers.  If  not  following
the  methods  of  the  installation  codes,  be  sure  that  any
accessory  you  choose  has  been  tested  by  an  independent
laboratory  and  carries  the  laboratory’s  testing  mark.
Make  sure  to  follow  all  of  the  manufacturer’s
instructions.
Always  contact  your  local  building  inspector  or  fire
officials  about  restriction  and  requirements  in  your  area.
Reminder,  it  is  the  local  officials  who  have  final  authority
in  the  installations  approval.
ALCOVE
The OSLO F500 can be installed in an ALCOVE
situation provided:
      
 See figures 9 and 10.
1.  The stove must be installed with listed double
     wall pipe.
2.  In a PROTECTED alcove installation both side
     walls and rear wall  must be protected per NFPA
     211 or CAN/CSA-B365.  The wall protection
     must be elevated 1” from the floor  and at least 1”
    off the combustible wall to allow  for an air-flow.
3.  The height of the wall protection including the
     bottom air space must be 48”.
4.  The Bottom heatshield is required in all Alcove
     installations.
5.  If a listed (UL/ULC) hearth board is NOT used
     the hearth that is constructed MUST have a
     minimum R value of 1.6 (see Appendix A).
6.  Minimum ceiling height in an unprotected installa
     tion, off the top of the stove is  41”(1040mm) The
     minimum ceiling height off the top of the stove  in
    a protected ceiling  installation is 15”(380mm).
7. ALCOVE floor protection must be: a UL/ULC
or WHI listed hearth pad or a non combustible
material with a minimum R value of 0.5.
In  Canada,  refer  to  CAN/CSA-B365,  Installation
Code  for  Solid-Fuel  Burning  Appliances  and
Equipment,  also  for  acceptable  materials,  proper
sizing and construction guidelines.
Stove Mounted Heatshield:  A stove rear heatshield
has been specifically  designed for the OSLO F500.
In  the  U.S.  and  Canada  the  rear  heatshield  part
number is # 154332.
NO   OTHER   HEAT  SHIELD   MAY   BE   USED.
MOBILE  HOME  INSTALLATIONS
The OSLO F500 has been approved for use in mobile
homes in the U.S. and Canada, provided:
1. The stove is secured to the floor or the mobile
home. Floor mounting kit #750304
2. The stove is provided outside air for combustion.
Outside Air kit  #154335(
see page 16 for more details)
3. The stove must be grounded to the mobile home
frame per NFPA 70.
As  always  consult  with  your  local  building
inspector or fire officials about restrictions and
requirements in your area, prior to installing the
stove.
56.5”  min.
(1435mm)
UNPROTECTED ALCOVE INSTALLATION
*
max.  depth
48”  (1220mm)
14”
355mm
14”
355mm
18”
460mm
* USE OF THE LEFT SIDE LOAD DOOR IS  PROHIBITED
   IN ALCOVE  INSTALLATIONS.
40.5”  min.
1015mm
  max.  depth
  48”  (1220mm)
PROTECTED ALCOVE INSTALLATION
*
* USE OF THE LEFT SIDE LOAD DOOR IS  PROHIBITED
   IN ALCOVE  INSTALLATIONS.
150mm
150mm
12”
300mm
PROTECTION
AND  AIR
SPACE  MUST
COMPLY
WITH  NFPA
211OR
CAN/CSA-B365.
10
FIGURE    9
FIGURE  10