Jotul F 3 Benutzerhandbuch

Seite von 21
WALL PASS-THROUGHS
When  your  installation  unavoidably  requires  the
chimney connector to pass through a combustible wall
to  reach  the  chimney,  always  consult  your  local
building officials, and be sure any materials to be used
have been tested and listed for wall pass-throughs.
In the U.S.
The National Fire Protection Association’s publication,
NFPA  211,  Standard  for  Chimneys,  Fireplaces,
Vents and Solid Fuel Burning Appliances  permits
four methods for passing through a combustible wall.
Before proceeding with any method be sure to consult
with your local building officials to discuss any local
code requirements.
Common Method
When  passing  through  a  combustible  wall  to  a
masonry chimney this method requires the removal
of all combustible materials from at least 12” around
the chimney connectors proposed location. With a 6”
round liner the minimum area required would be 31”
x 31” square.
The space is then filled with at least 12” of brick
around a fireclay liner.  Remember, the liner must be
ASTM  C35  or  equivalent,  with  a  minimum  wall
thickness of 5/8”.
It is important to remember to locate the pass-through
at least 18” from the ceiling for proper clearance to
combustibles.
It will be necessary to cut wall studs, install headers,
and  construct  a  sill  frame  to  maintain  the  proper
dimensions and  to support the weight of the brick.
The bricks must be solid brick with a minimum of
3 ½ “ thick (4” nominal).
Refractory mortar must be used at the junction of the
chimney and the pass-through liner.  The pass-through
liner must not penetrate the chimney liner beyond the
inner surface of the chimney liner.  Use extreme care
when constructing the hole in the chimney liner, the
tiles can shatter easily.  See figure 7
.
The manufacturer’s installation instructions must be
followed  precisely.   Always  maintain  the  proper
clearance to combustibles as established by the pipe
manufacturer.  This clearance is usually a minimum
of 2”, although it may vary by manufacturer or for
certain chimney components.
Chimney  Height
Whether a masonry chimney or prefabricated metal
chimney is used it must be the required height above
the roof line.
The requirement is:
The chimney must be at least 3 feet higher than the
highest point where it passes through the roof and at
least 2 feet higher than the highest part of the roof or
structure  that  is  within  10  feet  of  the  chimney,
measured horizontally. See figure 6.
Chimneys  shorter  than  14  feet  may  not  provide
adequate draft.  This could result is smoke spilling
into the room from the stove when loading the stove,
or when the door is open.  In addition, inadequate
draft can cause back puffing, which is a build up of
gases inside the firebox.
Other times, chimney height can create excessive
draft which can cause high stove temperatures and
short burn times.  Excessive drafts can be corrected
by installing a butterfly damper.  If you suspect you
have a draft problem, consult your dealer.
7
FIGURE 6