Lightolier FBP33 Merkblatt
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • C0308
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • C0308
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
FBP Series Fluorescent Emergency Ballast
FBP33
Page 1 of 1
Three Parallel Lamps Operation 3,400 Lumens
Lightolier is a Philips group brand
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
16.3”
(41.4 cm)
5.6”
(14.2 cm)
1.7”
(4.3 cm)
Features
1. Lamp Operation: Operates the following lamp types: T8 linear fluorescent,
and T5 long compact fluorescent. See Lamp Operation and Performance
table for specific lamp performance and operation.
table for specific lamp performance and operation.
2. Illumination: Provides 90 minutes of emergency illumination, and produces
a maximum of 3400 initial lamp lumens when used to power two or three
32W (4’) T8 fluorescent lamps, two or three 39W T4, or two 40 - 55W t4-4
pin long compact fluorescent lamps. Any non-emergency AC ballast used in
conjunction with the FPB33 MUST be an instant start, parallel output 2, 3, or
4 lamp regular or dimming type ballast.
32W (4’) T8 fluorescent lamps, two or three 39W T4, or two 40 - 55W t4-4
pin long compact fluorescent lamps. Any non-emergency AC ballast used in
conjunction with the FPB33 MUST be an instant start, parallel output 2, 3, or
4 lamp regular or dimming type ballast.
3. Housing: Constructed of 20 gauge steel with a white high temperature pow-
der coat paint finish. Slim housing allows for wireway channel mounting on
most recessed luminaires.
most recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and test
switch.
switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an estimated
service life of 10 years, and an operating temperature range of 32°F (0°C) to
131°F (55°C).
131°F (55°C).
6. Input Power Requirements: 8 watts max.
7. Warranty: Electronics: 5 years; Battery: 5 years
7. Warranty: Electronics: 5 years; Battery: 5 years
Code Compliance
UL 924 listing pending.
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact fac-
tory for other input voltages and frequencies.
tory for other input voltages and frequencies.
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot.
Complete Fixture consists of ballast unit. Select options and accessories below.
Model #
Max. Lumens
Lamp Operation
FBP33
3,400
Two or Three
Lamp Operation and Performance
Non-Emer. Emer. Op.
Max.
Max.
Emer.
Lamp
Base
Lumen
Lumen
Lamp
Type
Watt.
Type
Output
Output
Operation
F32T8
32
G13/Med Bi-Pin
2850
3400
Two or Three
F39/36BX
39
2G11/4--Pin
2850
3200
Two or Three
F40/30BX
40
2G11/4--Pin
3150
3200
Two
F50BX/FT55 50-55
2G11/4--Pin
4300-4800
3300
Two
Notes:
1. Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient operating
temperature, and ballast manufacturer.
2. Maximum emergency lumen output is based on total output of one or two lamps, and can vary
based on lamp manufacturer and ambient operating temperature.
3. Maximum emergency lumen output is supported for a full 90 minutes of operation.
4 Consult factory for compatibility, operation and performance of lamp types not listed.
4 Consult factory for compatibility, operation and performance of lamp types not listed.
Nickel Cadmium Battery