Lightolier FBP100FE Merkblatt
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • B0308
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • B0308
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
FBP Series Fluorescent Emergency Ballast
FBP100FE
Page 1 of 1
One Lamp Operation 350 - 450 Lumens
Lightolier is a Philips group brand
Nickel Cadmium Battery
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
9.4”
(23.9 cm)
2.4”
(6.1 cm)
1.5”
(3.8 cm)
NOTES:
1. Maximum non-emergency lumen output can vary
based on lamp manufacturer, ambient operating
temperature, and ballast manufacturer.
temperature, and ballast manufacturer.
2. Maximum emergency lumen output is based on total
output of one or two lamps, and can vary based on
lamp manufacturer and ambient operating tempera-
ture.
lamp manufacturer and ambient operating tempera-
ture.
3. Maximum emergency lumen output is supported for
a full 90 minutes of operation.
4. Consult factory for compatibility, operation and
performance of lamp types not listed.
NON-EMERGENCY
EMERGENCY OP.
LAMP
WATTAGE
BASE
MAX. LUMEN
MAX. LUMEN
EMERGENCY
TYPE
TYPE
OUTPUT
OUTPUT
LAMP OPERATION
F20T12
20
G13/Med Bi-Pin
1275
350 - 450
One
F30T12
30
G13/Med Bi-Pin
2350
350 - 450
One
F40T12
40
G13/Med Bi-Pin
2650
350 - 450
One
F40T12/U
40
G13/Med Bi-Pin
3100
350 - 450
One
F48T10
110
R17D/Recessed
6200
350 - 450
One
F17T8
17
G13/Med Bi-Pin
1350
350 - 450
One
F25T8
25
G13/Med Bi-Pin
2150
350 - 450
One
F32T8
32
G13/Med Bi-Pin
2950
350 - 450
One
F32T8/U
32
G13/Med Bi-Pin
2700
350 - 450
One
F40T8
40
G13/Med Bi-Pin
3725
350 - 450
One
FC6T9
20
G10Q/4 Pin
800
350 - 450
One
FC8T9
22
G10Q/4 Pin
1100
350 - 450
One
FC12T9
32
G10Q/4 Pin
1950
350 - 450
One
FC16T9
40
G10Q/4 Pin
2700
350 - 450
One
F39/36BX
39
2G11/4 Pin
2850
350 - 450
One
F40/30BX
40
2G11/4 Pin
3150
350 - 450
One
Lamp Operation and Performance
Features
1. Lamp Operation: Operates the following lamp types: T8 linear fluo-
rescent, T12 linear fluorescent, T9 circline, T12 U-bent, T5 long compact
fluorescent. See Lamp Operation and Performance table for specific lamp
performance and operation.
fluorescent. See Lamp Operation and Performance table for specific lamp
performance and operation.
2. Illumination: Provides 90 minutes of emergency illumination, and pro-
duces 350-450 lumens initial emergency light output. Can be used with
most 17w to 40w (2’ - 4’) T8, T10 or T12 fluorescent lamps without integral
starters including U-shaped, HO, VHO, circline, energy saving, and 4 pin
compacts. It is also compatible with most 1, 2, 3 and 4-lamp electronic,
standard, energy saving and dimming AC ballasts.
most 17w to 40w (2’ - 4’) T8, T10 or T12 fluorescent lamps without integral
starters including U-shaped, HO, VHO, circline, energy saving, and 4 pin
compacts. It is also compatible with most 1, 2, 3 and 4-lamp electronic,
standard, energy saving and dimming AC ballasts.
3. Housing: Constructed of 20 gauge steel with a white, high temperature
powder coat paint finish. Slim housing allows for wireway channel mount-
ing on most recessed luminaires.
ing on most recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and
test switch.
test switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an esti-
mated service life of 10 years, and an operating temperature range of 32°F
(0°C) to 131°F (55°C).
(0°C) to 131°F (55°C).
6. Input Power Requirements: 3.5 watts max.
7. Warranty: Electronics: 1 year; Battery: 1 year.
7. Warranty: Electronics: 1 year; Battery: 1 year.
Code Compliance
U.L. 924 listed.
Complete Fixture consists of ballast unit. Select options and accessories below.
Model #
Max. Lumens
Lamp Operation
FBP100
450
One
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact
factory for other input voltages and frequencies.
factory for other input voltages and frequencies.
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.