Honeywell 5820XL Benutzerhandbuch

Seite von 228
IntelliKnight 5820XL Installation Manual
7-8
151209
7. Then press 
.
7.4.1.3 Zone Outputs
Output groups and cadence patterns are mapped to events. They can be programmed to output 
when an event occurs in a zone. Some system trouble events can be mapped for the entire 
system. Section 6.2 of this manual contains a general explanation of mapping. The following 
sections explain how to select mapping options.
Note: Use of multiple notification groups may not synchronize with each other.
Mapping to Zone Events
Eight types of events can occur in zones. For each event type, you can activate up to 8 output 
groups or output group template, specifying a pattern for each. The following is a list of all 
event types:
Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see 
Manual Pull Alarm (MP)
Water Flow Alarm (WF)
Detector Alarm (DE). This applies to heat or smoke detectors.
Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.
Pre-alarm (PR)
Supervisory (SU)
Trouble (TR)
To map zone events to outputs:
1. From the Installer Main Menu, select 
 for Program Menu.
2. From the Program Menu, select 
 for Zone.
3. From the next menu, select 
 for Edit Zone.
4. Enter the zone number you wish to edit.
5. From the next menu, select 
 for Zone Outputs. 
6. From the next screen, a list of 8 event types will display. Select the event type you want to 
program. A screen similar to the one shown in Figure 7-3 will display. Press 
.
7. Press the 
 or 
 key to toggle the group letter to either G = Group or T = output group 
template depending on want you need for this zone. Press 
.
7
2
1
3