Honeywell 5820XL Benutzerhandbuch

Seite von 228
IntelliKnight 5820XL Installation Manual
7-18
151209
7.5.4
View Group Points
1. Enter the installer code.
2. Press 
 or 
 to display the main menu.
3. Select 
 for Program Menu.
Display reads:
Initializing
Please wait . . .
4. Press 
 to enter group menu.
5. Press 
 to view group points.
6. Enter the group number, then press 
.
7.5.5
Edit Output Group Templates
Some installations may require that zones be mapped to more than 8 output groups. With 
output group templates you can combine one or all output groups into one template, which can 
be used when the same combination of outputs are used for several zones.
For example, lets say an installation has five zones (See Table 7-4). The check mark indicates 
what output groups are mapped to each zone. You will notice that every zone is mapped to 
outputs 1 and 2. As an alternative you can create a template that combines output group 1 and 
2 as one choice. 
This can be done by creating a template which includes output groups 1 and 2. Then you can 
map all the zones to the template you created. This will free up  output group assignments that 
are common to several zones. This is very useful when you need to map zones to more than 
Table 7-4: Zone Group Example
Zone
Group Number
1
2
3
4
5
6
7
8
1st Floor Smoke Detectors
2nd Floor Smoke Detectors
3rd Floor smoke Detectors
Manual Fire Pull Stations
Water Flow Switches
7
3
4