Honeywell 5820XL Benutzerhandbuch

Seite von 228
IntelliKnight 5820XL Installation Manual
7-38
151209
7.7.4
Miscellaneous Options 1
Through this programming option you can set the water flow delay time, low AC report delay, 
enable or disable automatic daylight savings time adjustment, clock format, and AC clock 
frequency.
7.7.4.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction 
with a water flow switch. The delay is system-wide. All water flow switches on the system 
will use the same delay period. 
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Press 
 or 
 to display the main menu.
3. Select 
 for Program Menu.
Display reads:
Initializing
Please wait . . .
4. Select 
 for System Options.
5. Select 
 for Miscellaneous Options 1.
A screen similar to the one shown in Figure 7-16 will display.
Figure 7-16  Water Flow Delay Programming Screen
7
5
5
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)