System Operation
151209
8-11
8.6
Operation Mode Behavior
The control panel can be in one of seven conditions at any given moment: Normal, Alarm, 
Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the behavior of the 
panel in each of these modes. 
Table 8-1: Operation Mode Behavior
Operation 
Mode
Occurs When
System Behavior
In This Mode You Can
Normal
No alarm or 
trouble 
condition exists 
and menus are 
not in use.
SYSTEM POWER LED is on.
The All Systems Normal display indicates 
that the system is in normal mode.
The current date and time display on the 
last line of the LCD.
Enter the appropriate code to activate the User or 
Installer Menu, or rotate the key to activate the User 
Menu.
Alarm
A smoke 
detector goes 
into alarm or a 
pull station is 
activated.
The dialer seizes control of the phone line 
and calls the central station.
The on-board annunciator sounds a loud, 
steady beep (any notification devices 
attached to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this 
one.
Press the down arrow to view the alarm. A screen 
similar to this one displays.
Press 
 and enter an access code (or 
activate the key) to silence the annunciator (and any 
notification devices attached to the system).
When the alarm condition clears, press 
 
and enter a code (or activate the key) to restore the 
panel to normal.
SILENCE
RESET