Honeywell 5820XL Benutzerhandbuch

Seite von 228
151209
9-1
Section 9
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes sent 
by the control panel for SIA and Contact ID formats.
9.1
Receivers Compatible with the Control Panel
Table 9-1 shows receivers compatible with the control panel.
9.2
Reporting Formats Dialer Outputs  
Table 9-1: Receivers Compatible with the Control Panel
Manufacturer
Model
Format
Silent Knight
Model 9800
SIA and Contact ID
Model 9000 (SIA formats)
SIA
Ademco
Model 685 (Contact ID )
Contact ID
Sur-Gard
SG-MLR2-DG (V. 1.64 or higher)
SIA and Contact ID
Osborne Hoffman
Quickalert
SIA and Contact ID
SIA Reporting Format
Contact ID Reporting Format
Event Description
Event 
Family
Event Class 
(System, Zone, 
or Point)
Module
ID # 
(if any)
SIA
Event
Code
Parameter 
(if any)
Qualifier
Event
Code
Group
#
Contact
#
System Events
Note:
  Note: System events are reported when either "Report by Point" or "Report by 
Zone" is selected.
AC power restore
Trouble
System Event
AR
3
301
00
000
AC power lost
Trouble
System Event
AT
1
301
00
000
SBUS expander trouble restore
Trouble
System Event
ER
Exp. ID
3
333
00
Exp. ID
SBUS Class A supervision restore
Trouble
System Event
ER
Exp. ID
3
333
00
Exp. ID
Short circuit removed from SLC 
communication loop
Trouble
System Event
ER
Exp. ID
3
332
00
Exp. ID
SLC Class A supervision restored
Trouble
System Event
ER
Exp. ID
3
331
00
Exp. ID
SBUS expander trouble
Trouble
System Event
ET
Exp. ID
1
333
00
Exp. ID
SBUS Class A supervision lost
Trouble
System Event
ET
Exp. ID
1
333
00
Exp. ID
Short circuit detected on SLC com-
munication loop
Trouble
System Event
ET
Exp. ID
1
332
00
Exp. ID
SLC Class A supervision lost
Trouble
System Event
ET
Exp. ID
1
331
00
Exp. ID
Fire drill has begun
Test
System Event
FI
1
604
00
000
Fire drill ended
Test
System Event
FK
3
604
00
000
Panel date has been changed
Trouble
System Event
JD
1
625
00
000