Agency Listings, Approvals, and Requirements
151209
2-3
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 
30 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not 
be used in commercial applications whereby a general alarm is sounded. It is intended for 
elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL 
certified installations the setting must be a minimum of 60 seconds.
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm 
verification feature, and no delay shall be used.
P.A.S feature shall be used only with automatic detectors.
2.2.2
Requirements for Central Station Fire Alarm 
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5820XL sends an automatic 
daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 1-3 hours.
5. The Attempts to Report option must be set for 5.
2.2.3
Requirements for Local Protected Fire Alarm 
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4
Requirements for Remote Station Protected Fire 
Alarm Systems - Digital Alarm Communicator
Transmitter (DACT)
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 15-30 hours.