Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with 
telephone communication or cause false alarms. To avoid induced noise, follow these 
guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi-
conductor cable for the entire panel. Instead, separate the wiring as follows:
Do not pull wires from different groups through the same conduit. If you must run them 
together, do so for as short a distance as possible or use shielded cable. Connect the shield 
to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit 
board where it could induce noise into the sensitive microelectronics or pick up unwanted 
RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or 
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it 
around a ferrite toroid.
37
Ring
Phone Line 1 Telco Ring
N/A
0
Ω
38
Tip
Phone Line 1 Telco Tip
39
Ring
Phone Line 1 Premises Ring
40
Tip
Phone Line 1 Premises Tip
41
Ring
Phone Line 2 Telco Ring
N/A
0
Ω
42
Tip
Phone Line 2 Telco Tip
43
Ring
Phone Line 2 Premises Ring
44
Tip
Phone Line 2 Premises Tip
45
SC-
SLC Programming Terminal ( - )
32 VDC
150 mA
0
Ω
46
SC+
SLC Programming Terminal ( + ) 32 VDC
150 mA
High voltage
AC power, Terminals 1-3
SLC loops
Terminals 33-36
Audio input/output 
Phone line circuits, Terminals 
37-44
Notification circuits
Terminals 4-15
SBUS Terminals 
16-23
Relay circuits
Terminals 24-32
Terminal # and Label
Description
Rating
Earth Ground 
Faults
Voltage
Current