Honeywell 5820XL Benutzerhandbuch

Seite von 228
IntelliKnight 5820XL Installation Manual
3-6
151209
3.6
Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your 
installation.
3.6.1
Current Draw Worksheet Requirements
The following steps must be taken when determining 5820XL current draw and standby 
battery requirements.
1. You will use the Current Draw Worksheet to determine current draw and standby battery 
requirements. Use Table 3-1 if installing SK SLC Devices and Table 3-2 if installing 
Hochiki SLC Devices. For the 5820XL, the worst case current draw is listed for the panel, 
addressable devices, and all SBUS expanders. Fill in the number of addressable devices 
and expanders that will be used in the system and compute the current draw requirements 
for alarm and standby. Record this information in the Current Draw Worksheet on Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the 
device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, 
does not exceed 6.0 A. This is the maximum alarm current for the 5820XL control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as 
the Silent Knight 5495 or the 5895XL intelligent power expander, to distribute the power 
loads so that the 5820XL or the power expanders do not exceed their power rating. Refer 
to the current draw worksheets provided with the 5495 or the 5895XL manuals so you do 
not exceed their power requirements.
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for deter-
mining battery size requirements.