3-12
151209
3.6.4
Maximum Battery Standby Load
Table 3-3 shows the maximum battery standby load for the 5820XL based on 24 and 60 hours 
of standby. The standby load calculations of line D in the Current Draw Calculation 
Worksheet (Table 3-1 for SK devices and T
able 3-2 for Hochiki devices) must be less than the 
number shown in Table 3-3 for the battery size used and standby hours required
*  33AH max battery size for FM (Factory Mutual) installations..
*
Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote 
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter 
(DACT).
3.7
Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the 
IntelliKnight 5820XL system. The chart is intended to be a handy way for you to make sure 
you have completed all necessary tasks. Unless noted, these tasks do not have to be performed 
in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Table 3-3: Maximum Battery Standby Load
Rechargeable Battery Size
Max. Load for 24 hrs. 
Standby, 5 mins. Alarm
*Max. Load for 60 hrs. 
Standby, 5 mins. Alarm
7 AH
270 mA
105 mA
12 AH
475 mA
190 mA
18 AH
685 mA
270 mA
35 AH
1.3 A
540 mA
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table 3-3. If you use a battery 
too small for the installation, the system could overload the battery resulting in the installation having less than 
the required 24 hours standby power. Use Table 3-3 to calculate the correct battery amperes/hour rating needed 
for your installation.
Task
See Sec.
(for more info.)
Main Panel Hardware Installation
U
Mount the control panel cabinet.
U
Connect AC.
U
Connect phone lines.
U
Install 5815XL SLC expander modules (if needed). Required if more than 
127 SLC devices are used.
U
Install 5860 Remote Fire Alarm Annunciator modules if used.
U
Install 5865 or LED Annunciator modules if used.
U
Install 5880 LED I/O module if customized LED annunciation will be used. 
U
Install notification appliances.
U
Install auxiliary power devices (if used).
U
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.
U
Connect batteries (typically last step).