Honeywell 5820XL Benutzerhandbuch

Seite von 228
Control Panel Installation
151209
4-3
4.3
Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH 
rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase 
the AH rating. It is recommended that you replace batteries every five years.
Figure 4-2  Battery Connection
To Control Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Listed 12V Battery
UL Listed 12V Battery