4.13.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back
of this manual.
of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-31.
2. Configure the circuit for Class A in programming (see Section 7.6).
Figure 4-31 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-31 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
would be referred to as point 5.
Caution
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput
connectors. Break wire runs to provide supervision of connections.
connectors. Break wire runs to provide supervision of connections.
Supervised
Power Limited
Power Limited
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined