Control Panel Installation
151209
4-39
4.13.5 Auxiliary Power Installation
Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three 
types of auxiliary power available are:
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for 
all Flexput circuits must not exceed 6.0 A).
To install an auxiliary power circuit:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-38 for loca-
tion of Flexput circuits.
2. Configure the auxiliary power output through programming (see Section 7.6).
Figure 4-38  Flexput Circuit Location
4.13.5.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the 
system and the panel has AC power, door holder circuits have 24-volt power present at their 
terminals. Any alarm will cause power to disconnect. Power will be re-applied when the 
system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power 
will be disconnected to conserve the battery backup. When AC power is restored, power is 
immediately restored to the door holder circuits. 
Use a UL listed door holder ESL DHX-1224, for this application.
4.13.5.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is 
always present at Constant circuits.