IntelliKnight 5820XL Installation Manual
4-46
151209
4.15.5 Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay  is wired for polarity reversal, it reports alarm and trouble 
events to a remote site. Alarms will override trouble conditions and it will not be possible to 
reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current:
15 mA max.
Operating Voltage:
24 VDC nominal
Resistance:
4 K
Ω
To install the MR-201/T for polarity reversal, follow the steps below:
Figure 4-45  Wiring the MR-201/T
2. Program the Flexput circuit for non silence NAC circuit (see Section 7.6).
Intended for Connection 
to a Polarity Reversal 
Circuit of A Remote 
Station Receiving Unit 
Having Compatible 
Rating.