IntelliKnight 5820XL Installation Manual
5-10
151209
5.8.2
SLC Devices with Dip Switches
Input and relay module addresses are set using the dip switches on the module board. The 
chart below shows the available addresses. For example, to select address 3, place dip 
switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid 
address.            
Figure 5-8  Hochiki SLC Device Addressing Using Dip Switches