Honeywell IPGSM-DP Benutzerhandbuch

Seite von 16
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide 
 
– 11 – 
RF Specifications 
 
 
Band 
Transmission 
Frequency  
(MHz) 
Transmit 
Power  
(dBm) 
Receive 
Frequency 
(MHz) 
Receive 
Sensitivity 
(dBm) 
Number 
of 
Channels 
Channel 
Spacing 
(MHz) 
Duplex 
Separation 
(kHz) 
GSM 850 
824-849 33 
869-894 
-107 
124 
200 
45 
GSM 900 
890-915 33 
935-960 
-107 
124 
200 
45 
GSM 1800 
1710-1785 30 
1805-1880 
-106 
374 
200 95 
GSM 1900 
1850-1910 30 
1930-1990 
-105.5 
299 
200 80 
 
 
IPGSM-DP Specifications 
 
ITEM 
SPECIFICATION 
Cabinet Dimensions: 
Width = 12 3/4 inches  
Height = 14 7/8 inches  
Depth = 3 inches 
Transformer: N8167 
 
Primary – 120VAC, 60Hz 
Secondary – 18VAC, 50VA 
Battery: 
12V, 7Ah sealed lead acid type (not supplied) 
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.  
Battery Charging Current: 
maximum 1A 
Supervision: 
The AC power, backup battery, IP communications, and GSM 
communications are monitored.