3.2
Considerations for SMV 3000 Transmitter,  
Continued
RTD requirements
Use a two-, three-, or four-wire platinum 100 ohm (Pt100) Resistance
Temperature Detector with rated measurement range limits of –200 to
450 °C (–328 to 842 °F) per DIN 43760 standard (
α
 = 0.00385 
Ω
/
Ω
/
°
C)
as the input source for the process temperature PV.
Thermocouple
requirements
Use one of the thermocouple types listed in Table 4 as the input source for
the process temperature.
Table 4
Thermocouple Types for Process Temperature Sensor
Type
Rated Range Limits
Standard
°
C
°
F
E
0 to 1000
32 to 1832
IEC584.1
J
0 to 1200
32 to 2192
IEC584.1
K
–100 to 1250
–148 to 2282
IEC584.1
T
–100 to 400
–148 to 752
IEC584.1