Drawing Number:
Drawing Date:
H-2-E
September 07, 2008
NOTE: This drawing is not intended to describe a complete system and is not a replacement for a pro-
fessional engineering drawing. It is intended only as a guide and does not imply compliance with local 
building code requirements. Confer with local building officials before installation
. The Contractor or 
engineer is to determine the necessary components and configuration of the particular system to be in-
stalled. It is the responsibility of the engineer or contractor to ensure that the installation is in accordance 
with all local building codes.
21
Hot Water
Supply Line
1/4" Normally Open
Solenoid Valve
Normally Closed
Solenoid Valve
(Full size of supply line)
S
S
Vacuum
Breaker
Sub 1
Primary
NOTE:
outside building structure.   These are indicated 
by being above the dashed line.
line should be located inside the building 
structure. 
The vacuum breaker line should be located inside 
the building structure.
Route drain per local codes
Outdoor
On-Demand
Water Heater
Cold Water Supply Line 
Gas Supply Line 
On-Demand
Equipment List 
QTY
On-Demand Outdoor      2
Water Heaters
Electronic Connection *
* Refer to On-Demand Accessories 
  and Model Applicability for 
  electronic connection details.
NOTE:
Pipes and fittings can be installed
inside a pipe enclosure or recess
box and packed with insulation
for additional protection.
Domestic Hot Water - Optional Freeze Protection
2 Outdoor On-Demand Water Heaters
Preferred Piping Installation
Outdoor
On-Demand
Water Heater
IMPORTANT!
With electrical power supplied to a on-demand water heater, it will not freeze
in enviornments as cold as -30  F, when protected from direct wind exposure.
In the event of a power failure at temperatures below freezing, the water 
heater should be drained of all water to prevent freezing damage.
The unit may be drained manually or through the installation of the 
Optional solenoid valves as shown.
The electrical connections for the two solenoid valves should be tied to 
the 120 V power terminals provided on the PC Board of the water heater.
When the electrical power to the water heater fails, the cold water supply 
drain down solenoid valve opens, allowing the water heater and 
associated piping to drain.  Ensure that you run the drain for the solenoids 
per local codes.
o
Key
Pressure Relief  Valve
Check Valve
3/4" Union
3/4" Ball  Valve
Boiler Drain Valve
Solenoid Valve
S
Pressure Regulator
Circulating Pump
Mixing Valve