vent with an oil burning furnace, the vent pipe should enter 
the smaller common vent or chimney at a point above the 
large vent pipe.
multiple heater manifold
Figure 13 and Table 7 should be used for horizontally manifolding 
two or more heaters.
figure 13
fresh air openings for confined spaces
The  following  instructions  shall  be  used  to  calculate  the  size, 
number  and  placement  of  openings  providing  fresh  air  for 
combustion,  ventilation  and  dilution  in  confined  spaces.  The 
illustrations shown in this section of the manual are a reference 
for  the  openings  that  provide  fresh  air  into  confined  spaces 
only. DO NOT refer to these illustrations for the purpose of vent 
installation.  See  Venting  Installation  on  page  15  for  complete 
venting installation instructions.
outdoor air through two openings
figure 14
The  confined  space  shall  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top 
and one commencing within 12 inches (300 mm) of the bottom of 
the enclosure. The openings shall communicate directly with the 
outdoors. See Figure 14.
each opening shall have a minimum free area of 1 square inch 
per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating 
of all appliances installed in the enclosure. each opening shall 
not be less than 100 square inches (645 cm2). 
outdoor air through one opening
figure 15
Alternatively a single permanent opening, commencing within 12 
inches (300 mm) of the top of the enclosure, shall be provided. See 
Figure 15. The water heater shall have clearances of at least 1 inch 
(25 mm) from the sides and back and 6 inches (l50 mm) from the 
front of the appliance. The opening shall directly communicate with 
the outdoors or shall communicate through a vertical or horizontal 
duct to the outdoors or spaces that freely communicate with the 
outdoors and shall have a minimum free area of the following:
1.  1 square inch per 3000 Btu/hr (733 mm
2
 per kW) of the total 
input rating of all appliances located in the enclosure, and
2.  Not less than the sum of the areas of all vent connectors in 
the space.
outdoor air through two horiZontal ducts
figure 16
The  confined  space  shall  be  provided  with  two  permanent 
horizontal ducts, one commencing within 12 inches (300 mm) of 
the top and one commencing within 12 inches (300 mm) of the 
bottom of the enclosure. The horizontal ducts shall communicate 
directly with the outdoors. See Figure 16.
each duct opening shall have a minimum free area of 1 square 
inch per 2,000 Btu/hr (1100 mm
2
 per kW) of the aggregate input 
rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional 
area  as  the  free  area  of  the  openings  to  which  they  connect. 
The minimum dimension of rectangular air ducts shall be not less 
than 3 inches.