Honeywell T6570 Benutzerhandbuch

Seite von 12
T6570, T8570 Series
Digital Fan-Coil Thermostats 
PRODUCT DATA 
APPLICATION 
T6570 Series Digital Fan-Coil thermostats provide line voltage 
on/off control for fans, valves, compressors or auxiliary 
electric heaters in fan-coil and small air-conditioner 
applications. 
T8570 Series provides low voltage control of these functions. 
Models are available for control of single stage air-conditioner 
and various fan-coil units 
– 2-pipe.  
–  2-pipe with manual heat/cool changeover. 
–  4-pipe with manual heat/cool changeover. 
–  4-pipe with automatic heat/cool changeover. 
All models are suitable for multiple applications. Changes in 
output wiring and external links between wiring terminals can 
configure the thermostat for the appropriate application. 
The fan can also be controlled from the thermostat. In some 
cases it is wired to run continuously and can be switched off 
with the On/Off switch. Other models can be installed with fan 
running continuously or cycling with the thermostat. 
Compressors and auxiliary electric heaters can be controlled 
using a relay or contactor controlled by the thermostat. 
FEATURES 
  Simple user interface. 
  Attractive modern styling ideal for offices or hotels. 
  Digital display of ambient temperature, with user 
activated temperature display. 
  Digital display shows mode icons when cooling or
heating relays operate, or when energy savings mode
is active. 
  Push button setpoint adjustment. 
  Switches allow manual control of system operation
and fan speed. 
  Energy savings mode - external energy savings input 
from time switch, occupancy sensors or hotel cardkey 
overrides comfort setpoint with setback heating or
cooling setpoint. 
  Energy savings input configurable, normally open or
normally closed. 
  Proportional plus integral (P+I) control algorithm for 
precision temperature regulation. 
  Mounts directly onto wall or standard junction box or 
vertical junction box with optional adapter plate. 
  Installer setup mode allows changes of operating 
parameters. 
  Selectable °C or °F display. 
  Adjustable deadband (some models) for heat and cool
control. 
  Selectable energy savings setup cooling and setback
heating setpoints. 
  Adjustable maximum heating and minimum cooling 
setpoint limits. 
  Adjustable minimum relay off-times (heating or 
cooling) for compressor short-cycle protection. 
  EEPROM permanently retains user settings during 
power loss (no batteries required). 
  Capability to display temperature sensor failure for 
easier troubleshooting. 
  Optional remote sensor (T8575D only). 
Contents 
Application.........................................................................  1  
Features ............................................................................  1  
Specifications ....................................................................  2  
Ordering Information .........................................................  2  
Installation .........................................................................  3  
Operation...........................................................................  4  
Operating Modes...............................................................  5  
Wiring ................................................................................  6 
95C-10897-6