T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—4
22
Fig. 19. Use of external relay and transformer for 
auxiliary loads greater than 1.6A.
TROUBLESHOOTING GUIDE
Refer to Table 13 for troubleshooting information.
M4944
L1 
(HOT)
L2
1
1
2
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED.
RELAY REQUIRED (R8222 OR SIMILAR).
Q7300 SUBBASE
TO 
LOAD
AUXILIARY
RELAY
CONTACTS
A1
A2
A3
Table 13. Troubleshooting Information.
Symptom
Possible Cause
Action
Display will not come on. Thermostat is not being powered.
Check that X terminal is connected to the system 
transformer.
Check for 24 Vac between X and R or RH terminals.
— If missing 24 Vac:
— check if the circuit breaker is tripped; if so, reset 
the circuit breaker.
— check if the system fuse is blown; if so, replace 
the fuse.
— check if the HVAC equipment power switch on 
the is in the Off position; if so, set to the On 
position.
— check wiring between thermostat and HVAC 
equipment and replace any broken wires and 
tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Temperature display is 
incorrect.
Room temperature display has been 
reconfigured.
Enter Installer Setup number 37 and reconfigure the 
display.
Thermostat is configured for °F or °C 
display.
Enter Installer Setup number 14 and reconfigure the 
display.
Bad thermostat location.
Relocate the thermostat.
Display shows two dashes and a degree 
sign.
Installer Setup 22 is set for remote sensing and the 
sensor is missing or the circuit is open or shorted.
Temperature settings will 
not change.
(Example: Cannot set 
heating higher or cooling 
lower.)
Upper or lower temperature limits were 
reached.
Check the temperature setpoints:
Heating limits are 40 to 90°F (7 to 31°C)
Cooling limits are 45 to 99°F (9 to 37°C)
The setpoint temperature range stops 
were configured.
Check Installer Setup number 34 and 35 and reconfigure 
the setpoint stops.
Keypad is locked. When a locked key is 
pressed, LOC flashes on the LCD.
Reset DIP switch 1 on back of thermostat to enable 
keypad.
Enter Installer Setup number 25 or 40 and reconfigure 
keypad lockout level.
Unable to configure 
Installer Setup
Installer Setup is locked out.
Reset the DIP switch 1 on back of thermostat to enable 
keypad.