Honeywell T874 Benutzerhandbuch

Seite von 224
T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
25
60-2485—8
Low Temperature Lockouts
Some manufacturers of heat pumps have previously controlled 
their units so the compressor was locked out below a specified 
outdoor temperature. This was done because of the stress 
placed on the compressor by the very cold temperatures, and 
the fact that efficiency drops off at low temperatures.
Other manufacturers say that although efficiency is low at cold 
temperatures, the problem of starting the cold compressor is 
the most critical point. It is more important to keep the 
compressor running than to shut it off and try to restart it when 
the temperature warms up to +10°F (-12°C). Also the 
crankcase heater, which can run only when the compressor is 
off, compensates for the lower compressor efficiency. So, it is 
equitable to let the heat pump run even with a coefficient of 
performance (COP) slightly less than one, rather than to turn it 
off and have to run the crankcase heater.
NOTE: To determine the COP of a heat pump, use the fol-
lowing formula:
COP =
Btu Out/Btu we pay for or Btuh Capacity
Unit Wattage x 3.413 Btu/Watt
Another factor favoring this control strategy is that newer heat 
pump designs maintain a level of efficiency even at outdoor 
temperatures well below zero. Some brands do not reach 
1.0 COP until -25°F (-32°C).
Virtually all manufacturers now let the heat pump run 
continuously rather than lock it out at cold temperatures.
Heat Pumps with Dual Compressors
Staging residential sized heat pumps is a requirement that 
developed from the need to make heat pumps as efficient as 
possible. One of the methods used to improve overall 
seasonal efficiency is to reduce the amount of time the 
machine is operating in a transitional mode. Transitional mode 
is starting and stopping in addition to recovering from defrost. 
Under light loads, when the heat pump is cycling on and off, 
this can be a significant amount of time and can result in a 
significant efficiency reduction. Capacity control is one way to 
reduce the cycling rate and improve the efficiency.
Additional capacity control methods used on other 
refrigeration systems (unloading, multiple compressors) are 
not as likely to be seen on residential heat pumps.
With a single-stage heat pump, the compressor is normally 
controlled by the first stage and the auxiliary heat by the 
second stage. The T874G, N and R Thermostats are used for 
this purpose.
With a two-stage compressor, the two thermostat switches 
control the individual compressor stages. Auxiliary heat is 
controlled along with the compressor stage-two, by the 
thermostat second stage. It comes on with the compressor 
high speed if an outdoor thermostat—wired in series with it—
is made. See Fig. 35.
Fig. 35. Two-stage heat pump with two-stage thermostat.
The outdoor thermostat is set at the balance point with both 
heat pump stages running. So if the heat pump can control the 
heating load down to +20°F (-7°C), the auxiliary heat comes 
on with the second stage of the compressor.
In effect, this control strategy changes the heat input of the 
second stage, depending on the amount of heat needed. 
Additional stages of auxiliary heat can be added with or 
without the control of more outdoor thermostats, See Auxiliary 
Heat section.
Another way to control a two stage heat pump is with a three-
stage thermostat. The T874W is designed for this application 
as well as others. See Fig. 36.
The advantage of this system is that no auxiliary heat is used until 
there is an actual demand from the controlled space.
Fig. 36. Two-stage heat pump with three-stage thermostat.
Two speed Heat Pump
One way to control capacity is to use a two-speed 
compressor. The compressor runs at low speed for stage-one 
heating and cooling. The compressor runs at the low speed 
instead of cycling the heat pump on and off under some light 
load conditions. 
The high speed is stage-two cooling. The compressor runs on 
high speed when loads increase so the low speed can no 
longer handle the cooling load. This reduces cycling rate and 
improves capacity.
M5838
THERMOSTAT
HEAT 2
HEAT 1
OUTDOOR
THERMOSTAT
COMP. 
STAGE 2
AUXILIARY
HEAT 
COMP. 
STAGE 1
M5837
COMP. 
STAGE 2
THERMOSTAT
HEAT 2
HEAT 1
AUXILIARY
HEAT 
HEAT 3
COMP. 
STAGE 1