BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
17
63-4524—01
Objects Table
Table 5. Objects.
Object Name
Type and 
Instance
Object Property
TB
7200
C5x
14B
T
B
72
00F
5x14
B
TB
7300
A5x
14B
TB
7305
A5x
14B
TB
7300
C5x
14B
TB
7305
C5x
14B
TB
7350
C5x
14B
TB
7355
C5x
14B
T
B
73
00F
5x14
B
T
B
73
05F
5x14
B
T
B
73
50F
5x14
B
T
B
73
55F
5x14
B
Room Temperature
AV 7
Present_Value (R,W)
Room Temp Override
BV 8
Present_Value (R,W)
Outdoor Temperature
AV 9 
Present_Value (R,W)
Room Humidity
AV 10
Present_Value (R,W)
Room Humid Override
BV 11
Present_Value (R,W)
Supply Temperature
AI 12
Present_Value (R)
Dehumidification 
Lockout
BV 13
Present_Value (R,W)
AUX Command
BV 14
Present_Value (R,W)
Sequence of Operation
MV 15
Present_Value (R,W)
System Mode
MV 16
Present_Value (R,W)
Fan Mode
MV 17
Present_Value (R,W)
Occupancy Command
MV 18
Present_Value (R,W)
Keypad Lockout
MV 19
Present_Value (R,W)
Control Output
GRP 20
Present_Value (R)
PI Heating Demand
AV 21
Present_Value (R)
PI Cooling Demand
AV 22
Present_Value (R)
Dehumidification Status
BI 23
Present_Value (R)
Controller Status
GRP 24
Present_Value (R)
AUX Status
BI 25
Present_Value (R)
Heating Valve Status
MV 26
Present_Value (R)
Cooling Valve Status
MV 27
Present_Value (R)
Fan Status
MV 28
Present_Value (R)
BI 1 Status
BI 29
Present_Value (R)
BI 2 Status
BI 30
Present_Value (R)
UI 3 Status
BI 31
Present_Value (R)
Local Motion
BI 32
Present_Value (R)
Effective Occupancy
MV 33
Present_Value (R)
Controller Alarms
GRP 34
Present_Value (R)
Window Alarm
BI 35
Present_Value (R)