Siemens CE1U2353en01a Benutzerhandbuch

Seite von 26
21/26 
Siemens Schweiz AG 
User Manual OEM 
CE1U2353en01a 
HVAC Products 
The settings in detail 22. 
November 
2006 
Overtemperature protection  
 
Line no. 
Operating line 
5051 
Storage tank temp max  
 
If the storage tank reaches the maximum storage tank temperature set here, the 
collector pump will be deactivated. It will be released again when the storage tank 
temperature drops 1 °C below the maximum storage tank temperature. 
 
The protective collector overtemperature function can reactivate the collector pump 
until the storage tank
’ s safety temperature is reached. 
 
T
t
TSp
L
1°C
TSpMax
1
0
23
54Z
10
 
TSpMax   Storage tank temp max (operating line 5051) 
TSp 
  Actual value of the storage tank temperature 
  Storage tank charging: 1 = on, 0 = off 
 
 
DHW push 
 
Line no. 
Operating line 
5070 Automatic 
push 
Off 
On 
 
The DHW push can be triggered either manually or automatically.  
With the DHW push, the DHW is heated up once until the nominal setpoint is reached. 
 
Off  
The DHW push must be triggered manually. 
 
On 
If the DHW temperature falls below the reduced setpoint (operating line 1612) by at 
least 2 switching differentials (operating line 5024), one-time charging to the nominal 
DHW setpoint (operating line 1610) will take place again. 
 
The automatic DHW push only works when the DHW operating mode is activated. 
 
2.7 Configuration 
 
Building and room model 
 
Line no. 
Operating line 
6112 
Gradient room model 
 
The room model gradient gives the period of time in minutes room heating needs to 
raise the temperature by 1 °C. The setting made applies to all circuits. 
Storage tank temp max   
 
Automatic push 
 
Gradient room model