Polaris PC 130-34 2NV Benutzerhandbuch

Seite von 64
9
Vent Termination Locations
The air inlet and exhaust outlet must be installed with the 
following minimum clearances (see figure 6):
• 
Twelve inches (30 cm) above grade or maximum antici-
pated snow level.
• 
Twelve inches (30 cm) from any opening through which 
flue gases could enter the structure.
• 
Four feet (122 cm) horizontally and vertically from gas 
or electric meters, gas regulators, dryer vents, vent 
hoods, bathroom fan exhaust, attic fans and turbines.
• 
Two feet (61 cm) from an inside corner formed by two 
exterior walls. 
• 
Two feet from porches, decks, overhangs and  other 
obstructions.
In addition to maintaining the minimum clearances , the 
vent should terminate according to the following guidelines:
1.    Use only 2 inch pipe or a 2 inch concentric vent 
on the vent termination for 100,000 - 150,000 BTU/
Hr models. Do not expose any 3” X 2” reducers or 
bushings to outdoor ambient temperatures. 
    CAN/CSA B149.1 Section 8.14.8: 
2.  When terminating a vent under a veranda, porch or 
deck, venting must be installed in accordance to all lo-
cal and provincial codes or in the absence of local and 
provincial codes, please refer to the CAN/CSA B149.1.
3.   A vent shall not terminate less than 7 ft. (2.1 m) above 
a paved sidewalk or paved driveway that is located on 
public property.
4.    A vent shall not terminate in an area where children or 
animals could block pipes.
5.    A vent shall not terminate in a location that is too close 
to shrubs or bushes.
6.  Caulk all cracks, seams and joints within 6 feet (1.83 m) 
horizontally above and below the vent.
7.  Combustion air inlet termination and exhaust air termi-
nation must be located in the same pressure zone.
Figure 6: Minimum Clearances for Inlet/Outlet and Concentric Vent
A.  12 in (30 cm) min. clearance above grade, 
veranda, porch, deck, balcony, or maximum 
anticipated snow level.
B.  12 in (30 cm) min. clearance on top and side of 
window or door that may be opened. Maintain a 
36 in (91 cm) minimum clearance below a window 
or door that may be opened.
C.  Clearance to permanently closed window.**
D.  12 in (30 cm) min vertical clearance to ventilated 
soffit located above the terminal within a horizontal  
distance of 2 ft (61 cm) from the center line of the  
terminal.
E.  12 in (30 cm) min. clearance to unventilated soffit.
F.  Clearance to outside corner **
G.  2 ft (61 cm) clearance to inside corner formed by 
two exterior walls.
H.  4 ft (122 cm) clearance to each side of center line 
extending above meter/regulator assembly.
I.  4 ft (122 cm) clearance to service regulator vent 
outlet.
J.  12 in (30 cm) clearance to nonmechanical air 
supply inlet to building or the combustion air inlet 
to any other appliance.
K.  3 ft (91 cm) above if within 10 ft (3 m) horizontally of 
mechanical air supply inlet.
**Clearance in accordance with local installation codes and the requirements of the gas supplier. 
A.  12 in (30 cm) min. clearance above grade,    
 
veranda, porch, deck, balcony, or maximum    
 
anticipated snow level.
B.  12 in (30 cm) min. clearance on top and side of  
 
window or door that may be opened. Maintain         
 
a 36 in (91 cm) minimum clearance below a   
 
window or door that may be opened.
C.  Clearance to permanently closed window.**
D.  12 in (30 cm) min vertical clearance to ventilated  
 
soffit located above the terminal within a horizontal  
 
distance of 2 ft (61 cm) from the center line of the  
 terminal.
E.  12 in (30 cm) min. clearance to unventilated soffit.
F.  Clearance to outside corner. **
G.  2 ft (61 cm) clearance to inside corner formed by  
 
two exterior walls.
H.  3 ft (91 cm) within a height 15 ft (4.57 m) above the  
 meter/regulator 
assembly.
I.  4 ft (122 cm) clearance to service regulator vent outlet.
J.  12 in (30 cm) clearance to nonmechanical air  
 
supply inlet to building or the combustion air inlet to  
 
any other appliance.
K.  6 ft (1.83 m) clearance to mechanical air supply inlet.
US Installations
Canadian Installations