American Water Heater BCL3 95T199 6NOX Benutzerhandbuch

Seite von 52
29
draining and flushing
Burn harzard.
Hot water discharge.
Keep  hands   clear  of  drain
valve  discharge.
It is recommended that the water heater storage tank be drained 
and  flushed  every  6  months  to  reduce  sediment  buildup.  The 
water heater should be drained if being shut down during freezing 
temperatures.
to drain the water heater storage tank:
1.  Turn off the electrical supply to the water heater.
2.  Turn  off  the  gas  supply  at  the  Main  Gas  Shutoff  Valve  if 
the water heater is going to be shut down for an extended 
period.
3.  ensure the cold water inlet valve is open.
4.  Open a nearby hot water faucet and let the water run until 
the water is no longer hot.
5.  Close the cold water inlet valve to the water heater.
6.  Connect a hose to the water heater drain valve and terminate 
it to an adequate drain.
7.  Open the water heater drain valve and allow all the water to 
drain from the storage tank.
8.  Close  the  water  heater  drain  valve  when  all  water  in  the 
storage tank has drained.
9.  Close the hot water faucet opened in Step 4.
10.  If the water heater is going to be shut down for an extended 
period, the drain valve should be left open.
to flush the water heater storage tank:
1.  Turn off the electrical supply to the water heater.
2.  ensure the cold water inlet valve is open.
3.  Open a nearby hot water faucet and let the water run until 
the water is no longer hot. Then close the hot water faucet.
4.  Connect  a  hose  to  the  drain  valve  and  terminate  it  to  an 
adequate drain.
5.  ensure  the  drain  hose  is  secured  before  and  during  the 
entire flushing procedure. Flushing is performed with system 
water pressure applied to the water heater.
6.  Open the water heater drain valve to flush the storage tank.
7.  Flush the water heater storage tank to remove sediment and 
allow the water to flow until it runs clean.
8.  Close the water heater drain valve when flushing is completed.
9.  remove the drain hose.
10.  Fill the water heater - see Filling The Water Heater in this manual.
11.  Turn on the electrical supply to place the water heater back 
in operation.
12.  Turn on the gas supply to the water heater at the Main Gas 
Shutoff Valve.
13.  Allow the water heater to complete several heating cycles to 
ensure it is operating properly.
periodiC remoVal of lime deposits from 
tank type CommerCial water heaters
The amount of calcium carbonate (lime) released from water is 
in direct proportion to water temperature and usage, see chart.  
The higher the water temperature or water usage, the more lime 
deposits  are  dropped  out  of  the  water.  This  is  the  lime  scale 
which forms in pipes, heaters and on cooking utensils.
lime accumulation may affect the life of equipment, the efficiency 
of the heater, and fuel consumption characteristics. The usage of 
water softening equipment greatly reduces the hardness of the 
water. However, this equipment does not always remove all of 
the hardness (lime). For this reason it is recommended that a 
regular schedule for deliming be maintained.
The  time  between  cleaning  will  vary  from  weeks  to  years 
depending upon water conditions and usage.
The  depth  of  lime  buildup  should  be  measured  periodically. 
Heaters  equipped  with  cleanouts  will  have  about  2"  of  lime 
buildup  when  the  level  of  lime  has  reached  the  bottom  of  the 
cleanout opening. A schedule for deliming should then be set up 
based on the amount of time it would take for a 1" buildup of lime. 
It  is  recommended  that  the  water  heater  initially  be  inspected 
after 6 months.
example 1:
Initial inspection after 6 months shows 1/2" of lime accumulation. 
Therefore, the heater should be delimed once a year.
example 2:
Initial inspection after 6 months shows 2" of lime accumulation. 
Therefore, the heater should be delimed every 3 months.
figure 26.
deliming solVents
Un•lIMe is recommended for deliming. Un•lIMe is a patented 
food grade acid which is safe to handle and does not create the 
harmful fumes which are associated with other products.
Un•lIMe may be obtained from your dealer, distributor or water 
heater manufacturer. Order Part number 9005416105, 1 gallon, 
packed 4 gallons per case or Part number 9005417105, 5 gallon  
container.