American Water Heater BCG3 Benutzerhandbuch

Seite von 52
15
Openings must be installed to provide fresh air for combustion, 
ventilation and dilution in confined spaces. The required size for 
the openings is dependent on the method used to provide fresh 
air to the confined space AnD the total Btu/hr input rating of all 
appliances installed in the space.
exhaust fans
Where exhaust fans are installed, additional air shall be provided 
to replace the exhausted air. When an exhaust fan is installed 
in  the  same  space  with  a  water  heater,  sufficient  openings  to 
provide  fresh  air  must  be  provided  that  accommodate  the 
requirements for all appliances in the room and the exhaust fan. 
Undersized openings will cause air to be drawn into the room 
through the water heater’s vent system causing poor combustion. 
Sooting, serious damage to the water heater and the risk of fire 
or explosion may result. It can also create a risk of asphyxiation.
louVers and grilles
The free areas of the fresh air openings in the instructions that 
follow do not take in to account the presence of louvers, grilles or 
screens in the openings.
The  required  size  of  openings  for  combustion,  ventilation  and 
dilution air shall be based on the “net free area” of each opening. 
Where the free area through a design of louver or grille or screen 
is  known,  it  shall  be  used  in  calculating  the  size  of  opening 
required to provide the free area specified. Where the louver and 
grille design and free area are not known, it shall be assumed 
that wood louvers will have 25% free area and metal louvers and 
grilles will have 75% free area. non motorized louvers and grilles 
shall be fixed in the open position.
never obstruct the flow of ventilation air. If you have any doubts 
or questions at all, call your gas supplier. Failure to provide the 
proper amount of combustion air can result in a fire or explosion 
and cause property damage, serious bodily injury or death.
unConfined spaCe
An Unconfined Space is one whose volume IS nOT leSS ThAn 
50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the 
total input rating of all appliances installed in the space. rooms 
communicating directly with the space, in which the appliances 
are  installed,  through  openings  not  furnished  with  doors,  are 
considered a part of the unconfined space.
Makeup  air  requirements  for  the  operation  of  exhaust  fans, 
kitchen ventilation systems, clothes dryers and fireplaces shall 
also be considered in determining the adequacy of a space to 
provide combustion, ventilation and dilution air.
unusually tight ConstruCtion
In unconfined spaces in buildings, infiltration may be adequate to 
provide air for combustion, ventilation and dilution of flue gases. 
however, in buildings of unusually tight construction (for example, 
weather stripping, heavily insulated, caulked, vapor barrier, etc.) 
additional air must be provided using the methods described in 
the Confined Space section that follows.
Confined spaCe
A Confined Space is one whose volume IS leSS ThAn 50 cubic 
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input 
rating of all appliances installed in the space.
Venting installation
Venting
The InSTrUCTIOnS In ThIS SeCTIOn On VenTInG MUST 
Be  FOllOWeD  TO AVOID  ChOKeD  COMBUSTIOn  Or 
reCIrCUlATIOn  OF  FlUe  GASeS.    SUCh  COnDITIOnS 
CAUSe SOOTInG Or rISKS OF FIre AnD ASPhYXIATIOn.
heater must be protected from freezing downdrafts.
remove all soot or other obstructions from the chimney that will 
retard a free draft.
Type B venting is required with these heaters. For typical venting 
application see TeChnICAl DATA VenTInG on pages 18 and 19. 
This  water  heater  must  be  vented  in  compliance  with  all  local 
codes,  the  current  revision  of  the  national  Fuel  Gas  Code 
(AnSI-Z223.1) and with the Category I Venting Tables.
If any part of the vent system are exposed to ambient temperatures 
below 40°F it must be insulated to prevent condensation.
•  Do not connect the heater to a common vent or chimney with 
solid fuel burning equipment.  This practice is prohibited by 
many local  building codes as is the practice of venting gas 
fired equipment to the duct work of ventilation systems.
 
figure 11. 
figure 12.
•  Where a separate vent connection is not available and the vent 
pipe from the heater must be connected to a common vent with 
an oil burning furnace, the vent pipe should enter the smaller 
common vent or chimney at a point above the large vent pipe.