American Water Heater BCG3 Benutzerhandbuch

Seite von 52
28
CheCk the igniter assemBly and main Burners
At least once a year, check the igniter assembly, Figure 25, and 
the main burner, Figure 26, for proper operation.  refer to the 
following igniter assembly and main burner sections.
igniter assemBly
For access to igniter assembly, unfasten two screws to burner 
cover and remove.  locate the burner with the igniter assembly 
and remove screw holding burner to manifold.  Slide burner out 
to access igniter assembly.
Servicing of the igniter assembly includes keeping the igniter free 
of lint, scale or any other foreign debris.
figure 25. igniter
main Burner
The  main  burner,  Figure  26,  should  display  the  following 
characteristics:
•  Cause rapid ignition and carry across entire burner.
•  Give reasonably quiet operation during ignition, burning, and 
extinction.
•  Cause no excessive lifting of flame from burner ports.
figure 26.
If the preceding burner characteristics are not evident, check for 
accumulation of lint, scale or other foreign debris that restricts or 
blocks the air openings to the burner or heater.
nOTe:
1.  remove main burners from unit.
2.  Check that burner venturi and ports are free of foreign debris.
3.  Clean burners with bristle brush and/or vacuum cleaner - DO 
nOT distort burner ports or igniter location.
4.  reinstall burners in unit.  Make sure front and rear of burners 
are installed correctly in burner support brackets.
Also check for good flow of combustion and ventilating air to the 
unit.  Maintain a clear area around the heater at all times.
Venting system
examine the venting system every six months for obstructions 
and/or deterioration of the vent piping.
remove all soot or other obstructions from chimney which will 
retard free draft.
remote storage tank temperature Control
The  water  temperature  in  the  remote  storage  tank  (if  used)  is 
controlled by the storage tank temperature control.  The sensing 
element  is  mounted  in  the  hot  water  storage  tank,  see  Water 
Piping Diagram section.
A change in water temperature in the storage tank lower than 
the  tank  temperature  control  setting  will  cause  the  sensor  to 
activate the circulating pump. The pump then circulates the water 
through the heater where the thermostat senses the drop in water 
temperature and activates main burner operation of the appliance.
If the storage tank temperature control is out of calibration, replace 
with new control.
ShOUlD OVerheATInG OCCUr Or The GAS SUPPlY FAIl 
TO ShUT OFF, TUrn OFF The MAnUAl GAS COnTrOl VAlVe 
TO The APPlIAnCe.
temperature-pressure relief ValVe test
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.
It is recommended that the Temperature-Pressure relief Valve should 
be checked to ensure that it is in operating condition every 6 months.
When checking the Temperature-Pressure relief Valve operation, 
make sure that (1) no one is in front of or around the outlet of the 
Temperature-Pressure relief Valve discharge line, and (2) that the 
water discharge will not cause any property damage, as the water 
may be extremely hot. Use care when operating valve as the valve 
may be hot.
To check the relief valve, lift the lever at the end of the valve several 
times, see Figure 27. The valve should seat properly and operate 
freely.
If after manually operating the valve, it fails to completely reset and 
continues to release water, immediately close the cold water inlet 
to the water heater and drain the water heater, see Draining And 
Flushing on page 29. replace the Temperature-Pressure relief 
Valve with a properly rated/sized new one, see Temperature-Pressure 
relief Valve on pages 13-14 for instructions on replacement.
figure 27.
If the Temperature-Pressure relief Valve on the water heater weeps 
or discharges periodically, this may be due to thermal expansion.
nOTe: excessive water pressure is the most common cause of 
Temperature-Pressure  relief  Valve  leakage.  excessive  water 
system pressure is most often caused by "thermal expansion" 
in a "closed system." See Closed Water Systems and Thermal 
expansion on page 13. The Temperature-Pressure relief Valve is 
not intended for the constant relief of thermal expansion.
Temperature-Pressure relief Valve leakage due to pressure build 
up in a closed system that does not have a thermal expansion 
tank installed is not covered under the limited warranty. Thermal 
expansion tanks must be installed on all closed water systems.
DO  nOT  PlUG  The  TeMPerATUre-PreSSUre  relIeF 
VAlVe  OPenInG. ThIS  CAn  CAUSe  PrOPerTY  DAMAGe, 
SerIOUS InJUrY Or DeATh.