Troubleshooting Common Service Problems
As a first step in diagnosis and troubleshooting, the unit should be disconnected from power at the breaker/fuse 
panel for ten seconds, then reconnect power to the unit and determine if the noted error code still appears.  The 
process of waiting for the error code to reappear may take about 8 minutes for the initial power initialization of 
the unit.
PROBLEM
POSSIBLE CAUSE
TEST/CORRECTIVE 
ACTION
NO HOT WATER:
No power to the water heater.
Check for blown fuse or tripped 
breaker. Restore power to the unit 
then press power button.
On/Off switch is off.
Press On/Off switch, should be 
illuminated green when energized.
Unit in Vacation mode.
Press Vacation button to turn off.
High temperature limit switch open Reset the high temperature limit 
switch; see “ECO Switch Trouble-
shooting” (p.25)
Non-functioning upper 
temperature sensor
Perform temperature sensor 
resistance test procedure (p.32), 
replace sensor if defective.
Inlet or outlet water valves at the 
water heater closed
Insure valves are fully open
INSUFFICIENT HOT WATER 
/ SLOW HOT WATER 
RECOVERY:
Temperature set point too low
Increase set point temperature; 
see “Adjusting Set Point 
Temperature” section (p.13)
Inlet or outlet valves at the water 
heater are partially closed
Insure valves are fully open
Air fi lter dirty
Clean or replace air fi lter
Hot water usage pattern exceeds 
the capability of the water heater 
in current mode
Change to diffrent mode or modify 
usage patterns
Water connections to unit reversed Ensure the cold connection is at 
the bottom and the hot connection 
is at the top
Heat lost through long run of 
exposed pipe
Insulate exposed piping.
Hot water leak at faucet or piping
Repair hot water leaks
Non-functioning heating element
Test elements and replace as 
required; see details in the 
“Element Test” section (p.22-23)
Sediment or scale build up in tank
Drain and fl ush tank. Water 
conditioning may be necessary to 
minimize build up.
Water heater may be under-sized
Upgrade to larger capacity water 
heater