Potential Installation Issues
Symptom
Cause
Solution
Temperature set to 60 ºF and not 
adjustable
Vacation mode is on
Turn off Vacation mode by pressing 
the Vacation button 
Electric mode selected but the 
heat pump is running
Upon initial start up, the heat 
pump will run until the tank 
temperature reaches the set 
point; this is done so that the 
heat pump operation can be 
verified.  The water heater 
will operate according to the 
selected mode after this first 
run.
No action is necessary.
If after heat pump operation has 
been verified and element heating 
is desired, lower the set point 
temperature to 95ºF.  The heat 
pump will shut off when the tank 
temperature is ≥ 95º F.  Set the 
temperature to the desired set point.  
The elements will now be used for 
heating in Hybrid and Electric modes. 
Power is applied to the unit, but 
there is no display on the User 
Interface Module (UIM)
The unit is in Standby; the 
power button on the UIM is 
RED
Press the power button; it should turn 
green and the display should light 
up.  If the power button does not turn 
green, remove the protective film 
over the face of the UIM and re-try 
the power button.
If the unit does not power up, cycle 
power to the unit and re-try using a 
thumb.
“Low Water Level Alarm” message 
displayed on the UIM
The tank is not completely 
filled with water
Purge air from the tank using the 
procedure outlined in the “Dry Fire 
Element Protection” section (p.8).
If the tank is properly filled, the unit 
should operate normally.
“Heat Pump Fault” message 
displayed on the UIM
There are 12 potential causes 
for this fault
Refer to the Trouble Shooting section 
for corrective actions (p.39-44)
Efficiency mode selected but 
elements come on instead of heat 
pump
Ambient air or water 
temperature outside the heat 
pump safe operating envelope
Heat pump safety lock out occurs if :
• 
ambient air temperature is       
below 45º F or above 109º F;
• 
tank temperature is below 59º F