American Water Heater HPE10260H045DV Benutzerhandbuch

Seite von 48
32
  
Temperature Sensors
Overview: 
The temperature sensors used in this water heater are 
negative temperature co-effi cient (NTC) thermisitors. 
With this type sensor, as temperature increases, 
the resistance across the thermisitor decreases or 
as temperature decreases, resistance will increase. 
The control board monitors the resistance of each 
sensor and converts each to a corresponding 
temperature. There are fi ve (5) such sensors 
installed on the heat pump water heater to monitor 
ambient, evaporator (coil), upper tank, lower tank and 
compressor discharge temperatures. Each is critical 
to the operation of the unit. If there is a connection 
issue with any sensor, there should be a connection 
fault displayed on the User Interface Module (UIM) 
Maintenance Display see “Accessing the Maintenance 
Display” (p.21).
The water heater can continue to heat water with a 
faulty temperature sensor, but operation will be affected 
as follows:
• 
The unit can function with a faulty lower tank 
temperature sensor. Upper tank temperature will 
be used in place of average tank temperature.
• 
A fault with the ambient, compressor discharge 
or coil (evaporator outlet) temperature sensor will 
cause a HEAT PUMP fault, locking out the heat 
pump. The unit will operate as if in ELECTRIC 
mode until the problem is resolved and the fault is 
cleared.
• 
An upper tank temperature sensor fault will lock 
out all water heating means, both heat pump and 
elements, until the problem is resolved and the 
fault is cleared.
NOTE: After the problem is resolved, a fault must 
be cleared by turning off power to the unit at the 
breaker or fuse panel for ten (10) seconds and 
then turning it back on. 
Temperature Sensor Resistance 
Measurement:
If a temperature sensor connect fault is indicated by 
the Maintenance Display or if a temperature sensor 
issue is suspected, use the following procedure to 
check the sensor(s):
1.  Check the resistance of a suspect temperature 
sensor by disconnecting the appropriate connector 
from the control board and placing the meter leads 
on the corresponding connector pins (see Table 4). 
Note that there are contacts located on the side of 
each connector that should be used.
2.  Note the ambient temperature.
3.  Compare the resistance reading on the appropriate 
Resistance vs. Temperature graph for the sensor 
being checked. If the reading is within ±2% of the 
value obtained from the graph, the sensor is good. 
If the value is outside this tolerance, the sensor 
should be replaced.
A more thorough check of a sensor can be done by 
checking at high and low temperature extremes. Check 
at low temperature by placing the sensor in ice. The 
reading should be 32°F. High temperature can be 
checked also, but do not exceed 130°F for the ambient 
sensor. All other sensors can be checked up to the 
boiling point (212°F). Submerge only the end of the 
sensor in boiling water; do not submerge the wire.
TABLE 5
Sensor
Connector / 
Pins
Chart
Ambient
CN212
Pins 1 to 2
Chart #1
Coil-
Evaporator
CN212
Pins 5 to 6
Chart #1
Tank-Upper
CN204
Pins 1 to 2
Chart #2
Tank-Lower
CN204
Pins 3 to 4
Chart #2
Discharge-
Compressor
CN212
Pins 3 to 4
Chart #2