American Water Heater VG6250T76NV Series 100 Benutzerhandbuch

Seite von 40
12
Such a condition often will result in a yellow, luminous burner 
flame, causing sooting of the combustion chamber, burners and 
flue tubes and creates a risk of asphyxiation.
Do  not  install  the  water  heater  in  a  confined  space  unless  an
adequate supply of air for combustion and ventilation is brought in 
to that space using the methods described in the Confined Space
section that follows. 
Never obstruct the flow of ventilation air. If you have any doubts or
questions at all, call your gas supplier. Failure to provide the proper 
amount of combustion air can result in a fire or explosion and cause
property damage, serious bodily injury or death.
unconfIned space
An Unconfined Space is one whose volume is not less than 50 cubic
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input
rating of all appliances installed in the space. Rooms communicating 
directly with the space, in which the appliances are installed, through 
openings  not  furnished  with  doors,  are  considered  a  part  of  the 
unconfined space.
Makeup air requirements for the operation of exhaust fans, kitchen 
ventilation systems, clothes dryers and fireplaces should also be
considered  in  determining  the  adequacy  of  a  space  to  provide 
combustion, ventilation and dilution air.
unusuallY tIGht constructIon
In unconfined spaces in buildings, infiltration may be adequate to
provide air for combustion, ventilation and dilution of flue gases.
However, in buildings of unusually tight construction (for example,
weather  stripping,  heavily  insulated,  caulked,  vapor  barrier,  etc.)
additional air must be provided using the methods described in the 
Confined Space section that follows.
confIned space
A Confined Space is one whose volume is less than 50 cubic feet
per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating
of all appliances installed in the space.
Openings  must  be  installed  to  provide  fresh  air  for  combustion, 
ventilation and dilution in confined spaces. The required size for the
openings is dependent on the method used to provide fresh air to 
the confined space and the total Btu/hr input rating of all appliances
installed in the space.
dIrect vent applIances
Appliances  installed  in  a  Direct  Vent configuration  that derive  all
air  for  combustion  from  the  outdoor  atmosphere  through  sealed 
intake air piping are not factored in the total appliance input Btu/hr 
calculations used to determine the size of openings providing fresh 
air into confined spaces.
eXhaust fans
Where exhaust fans are installed, additional air should be provided 
to replace the exhausted air. When an exhaust fan is installed in 
the same space with a water heater, sufficient openings to provide
fresh air must be provided that accommodate the requirements for 
all appliances in the room and the exhaust fan. Undersized openings 
will cause air to be drawn into the room through the water heater’s
vent system causing poor combustion. Sooting, serious damage to 
the water heater and the risk of fire or explosion may result. It can
also create a risk of asphyxiation.
louvers and GrIlles
The free areas of fresh air openings in instructions that follow do not take 
in to account presence of louvers, grilles or screens in openings.
The required size of openings for combustion, ventilation and dilution 
air should be based on the “net free area” of each opening. Where
the free area through a design of louver or grille or screen is known, it 
should be used in calculating the size of opening required to provide the 
free area specified. Where the louver and grille design and free area
are not known, it should be assumed that wood louvers will have 25% 
free area and metal louvers and grilles will have 75% free area. Non 
motorized louvers and grilles should be fixed in the open position.
fresh aIr openInGs for confIned spaces
The  following  instructions  should  be  used  to  calculate  the  size, 
number and placement of openings providing fresh air for combustion, 
ventilation and dilution in confined spaces. The illustrations shown in
this section of the manual are a reference for the openings that provide 
fresh air into confined spaces only. Do not refer to these illustrations
for the purpose of vent installation. See Installation of Vent System on 
pages 18-27 for complete venting installation instructions.
outdoor aIr throuGh two openInGs
fIGure 6.
The  confined  space  should  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. The openings should communicate directly with 
the outdoors. See Figure 6.
Each opening should have a minimum free area of 1 square inch 
per 4,000 Btu/hr (550 mm
2
per kW) of the aggregate input rating
of all appliances installed in the enclosure. Each opening should 
not be less than 100 square inches (645 cm
2
).
outdoor aIr throuGh one openInG
fIGure 7.
Alternatively a single permanent opening, commencing within 12 
inches (300 mm) of the top of the enclosure, should be provided. See